3.3 Dual Watchdog Operation

Dual Watchdog = Module Watchdog + Host Watchdog

The Module Watchdog is a hardware reset circuit that

monitors the module’s operating status. When working in harsh or

noisy environment, the module may go down by a noise signal. The

Module Watchdog times out and sets output to PowerOn value.

The Host Watchdog is a software function to monitor the

host’s operating status. Its purpose is to detect a network communi-

cation problem or a halted host. When the timeout interval expired,

the module will put all outputs to the predefined Safe Value. This

places the controlled element in a known-safe condition.

The CB-7000 module with Dual Watchdog makes the

control system more reliable and stable.

3.4 Reset Status

The Reset Status is set while the module power on or reset

by Module Watchdog, and is cleared when the Command read

Reset Status ($AA5) is applied. This is useful for user to check the

module’s working status. When the Reset Status is set means the

module is reset and the output may be changed to the PowerOn

Value. When the Reset Status is clear means the module is not

reset, and the output cannot be changed.

3.5 Digital Output

A module’s output can have one of three values:

1. Safe Value. If the host watchdog timeout status is set,

the output is set to Safe Value.If the module receives an output