CB-7000 DIO Manual

2.7 $AA5

Description: Read Reset Status

Command: $AA5[CHK](cr)

$

Delimiter character

AA

Address of reading module (00 to FF)

5

Command for read reset status

Response:

Valid Command:

!AAS[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid Command

?

Delimiter for invalid Command

AA

Address of response module(00 to FF)

S

Reset status, 1 = the module has been reset,

0 = the module has not been reset.

Example:

Command: $015

Receive: !011

Read Address 01 reset status, return first read.

Command: $015

Receive: !010

Read Address 01 reset status, return no reset occurred.