1 %aannttccff – Measurement Computing CB-7000 DIO User Manual
Page 28
28
CB-7000 DIO Manual
2.1 %AANNTTCCFF
Description: Set module Configuration
Syntax: %AANNTTCCFF[CHK](cr)
%
Delimiter character
AA
Address of setting module (00 to FF)
NN
New Address for setting module (00 to FF)
TT
Type 40 for DIO module
CC
New baud rate for setting module (Ref. Sec. 1.9). Short
INIT* to ground when changing baud rate. (Ref Sec. 3.1)
FF
New data format for setting module (Ref. Sec. 1.9). Short
the INIT* to ground to change checksum setting. (Ref.
Sec. 3.1)
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid Command
?
Delimiter for invalid Command
AA
Address of response module(00 to FF)
Example:
Command:
%0102400600
Receive: !02
Set module Address 01 to 02; return successful.
Related Command:
Sec. 2.5 $AA2
Related Topics:
Sec. 1.9 Configuration Tables, Sec. 3.1 INIT* pin Operation