2.1 %AANNTTCCFF

Description: Set module Configuration

Syntax: %AANNTTCCFF[CHK](cr)

%

Delimiter character

AA

Address of setting module (00 to FF)

NN

New Address for setting module (00 to FF)

TT

Type 40 for DIO module

CC

New baud rate for setting module (Ref. Sec. 1.9). Short

INIT* to ground when changing baud rate. (Ref Sec. 3.1)

FF

New data format for setting module (Ref. Sec. 1.9). Short

the INIT* to ground to change checksum setting. (Ref.

Sec. 3.1)

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid Command

?

Delimiter for invalid Command

AA

Address of response module(00 to FF)

Example:

Command:

%0102400600

Receive: !02

Set module Address 01 to 02; return successful.