Measurement Computing CB-7000 DIO User Manual
Page 32
32
CB-7000 DIO Manual
Assume module is CB-7067, set Address 02 channel 0 on, re-
turn is successful.
Command: #021701
Receive: ?
Set Address 02 channel 7 on, return the channel is invalid for
CB-7067; it only has seven outputs (0 to 6).
Command: #0300FF
Receive: !
Set Address 03 output value FF, return ignore. The module’s
host watchdog timeout status is set, and the output is set to
Safe Value.
Related Command:
Sec. 2.15 @AA(Data), Sec. 2.18 ~AA0, Sec. 2.19 ~AA1
Related Topics:
Sec. 1.9 Configuration Tables, Sec. 3.2 Module Status, Sec. 3.3
Dual Watchdog Operation
Note:
The Command is not for CB-7041/41D/52/52D/53/53D.
This manual is related to the following products: