5 $aa2 – Measurement Computing CB-7000 DIO User Manual
Page 34
34
CB-7000 DIO Manual
2.5 $AA2
Description: Read Configuration
Command: $AA2[CHK](cr)
$
Delimiter character
AA
Address of reading module (00 to FF)
2
Command for read configuration
Response:
Valid Command:
!AATTCCFF[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid Command
?
Delimiter for invalid Command
AA
Address of response module(00 to FF)
TT
Type code of module; it must be 40
CC
Baud rate code of module (Ref. Sec. 1.9)
FF
Data format of module (Ref. Sec. 1.9)
Example:
Command: $012
Receive: !01400600
Read Address 01 status, return DIO mode, baud 9600, no
checksum.
Related Command:
Sec. 2.1, %AANNTTCCFF
Related Topics:
Sec. 1.9, Configuration Tables; Sec. 3.1, INIT* pin Operation
This manual is related to the following products: