16 ~aao(data) – Measurement Computing CB-7000 DIO User Manual
Page 46
46
CB-7000 DIO Manual
2.16 ~AAO(Data)
Description: Set Module Name
Command: ~AAO(Data)[CHK](cr)
~
Delimiter character
AA
Address of setting module (00 to FF)
O
Command for set module name
(Data)
New name for module, max 6 characters
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
!
Delimiter for valid Command
?
Delimiter for invalid Command
AA
Address of response module(00 to FF)
Example:
Command: ~01O7050
Receive: !01
Set Address 01 module name 7050, return successful.
Command: $01M
Receive: !017050
Read Address 01 module name, return name 7050.
Related Command:
Sec. 2.10, $AAM
This manual is related to the following products: