3. Application Notes

3.1 INIT* pin Operation

Each CB-7000 module has a build-in EEPROM to store

configuration information such as address, type, baud rate and other

information. Sometimes, a user may forget the configuration of the

module. Therefore, the CB-7000 have a special mode named “INIT

mode”, to help user to resolve the problem. The “INIT mode” is

setting as Address=00, baud rate=9600bps, no checksum

To enable INIT mode, please follow these steps:

Step 1.

Power-down the module.

Step 2.

Connect the INIT* pin to the GND pin.

Step 3.

Power-up the module.

Step 4.

Send Command $002(cr) in 9600 bps to read the

configuration stored in the module’s EEPROM.

Refer to “7000 Bus Converter User ManualSec. 5.1

and “Getting Started” for more information.

3.2 Module Status

PowerOn Reset or Module Watchdog Reset will set all

outputs to the PowerOn Value. The module can accept the host’s

Command to change the output value.

Host Watchdog Timeout will set all output to the Safe

Value.The module’s status (read by Command ~AA0) will be 04,

and the output Command will be ignored.