beautypg.com

Legrand 881AMD8TC User Manual

Page 6

background image

6

Pass-through

Knock Out

Cut Slot in Gasket for

cable pass-through

Slide Mounting Screw

(2) #6-32

Align Gasket over

Flange and press

bead into Flange

CAUTION: Gasket must be set in

place to provide scrub
water seal. Do not
over-tighten cover
mounting screws.

2. Remove the slide cover and gasket to

facilitate the routing of the
communication cables.

3. For communication cable pass-through,

remove the egress knockout(s) located
on the underside of the cover.

4. Pull communication cables through box. Route one of the

cables around the receptacle for cable egress opposite the
communication compartment in the floor box. Reattach
slide cover with (2) #6 screws. Pass through cabling must
pass through internal gasket and slide cover.

899CTC COVER INSTALLATION:

5. Connect receptacle leads to circuit conductors with

twist-on wire connector or other approved methods.
See schematic below.

CAUTION: Receptacle mounting means not

grounded. Grounding wire
connection required. For isolated
ground wiring, connect ground
leads to a separate isolated
grounding conductor (see NEC
250-146(d)).

WHITE or NEUTRAL
from branch circuit

WHITE

from slide cover receptacle

BLACK or HOT
from branch circuit

BLACK
from slide cover receptacle

GREEN (jumper wire)

from cover adapter ring

GREEN

from slide cover receptacle

CONVENTIONAL WIRING SCHEMATIC

WHITE or NEUTRAL
from branch circuit

WHITE
from slide cover receptacle

BLACK or HOT

from branch circuit

BLACK
from slide cover receptacle

GREEN (jumper wire)
from cover adapter ring

ISOLATED GROUND
from branch circuit

GREEN
from slide cover receptacle

ISOLATED GROUND WIRING SCHEMATIC

GREEN or GROUND
from branch circuit
SYSTEM GROUND

GREEN or GROUND
from branch circuit
SYSTEM GROUND

6. If circuit is connected to an isolated ground, apply

IG Icon on receptacle slide as shown.

CAUTION: Receptacle supplied with this activation is not

suitable for direct field wiring. Contact manufacturer
for replacement. Field modifications will void UL
Listing. Replacement receptacle is limited to this
manufacturer’s catalog No. RC9REC.

NOTE: The orange triangle shall only be placed on

devices that are wired for isolated ground.
See NEC 250-146(d).

7. Orient the open side of the cover adapter with the divided

side of the box and push into place – No glue required!

1. Cut a 6 1/2" [165mm] circular

concentric opening in the floor
covering.

This manual is related to the following products: