beautypg.com

Greenheck Microprocessor Controller (474706 IOM) TAP v1.04 June 2011 (ERCH, ERH, APEX, VER, ERT) User Manual

Page 9

background image

9

DDC Controller for Tempered Air Products

Heating Status

Heater Control:

000%

Hot Gas Reheat:

000%

Staged reheat is:

ON

Compressor:

1 2

STATUS LINE

Preheat Status

Preheat:

OFF

STATUS LINE

h

eaT

and

reheaT

operaTion

is

displayed

. (

if

equipped

)

Heater Control displays the proportional percentage of the heater analog
output.
Electric Heater: The Heater Control % is proportional to the 0-10 VDC signal
being sent to the SCR controller, located in the electric heater control center.
0% Heating = 0 VDC - 0 kW output

100% Heating = 10 VDC - Max kW output

Hot Water: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the heating control valve (BY OTHERS). The heating control output
can be configured to DIRECT / REVERSE acting, along with the minimum and
maximum output voltages by entering the MANUFACTURER menu.
0% Heating = 0 VDC

100% Heating = 10 VDC

Indirect Gas: The Heater Control % is proportional to the 0-10 VDC signal
being sent to the indirect gas furnace controller, located in the indirect gas
control center. The first stage is on at 1% Heater Control. The furnace will then
modulate proportionally from minimum to maximum capacity.
0% = 0 VDC – OFF
1% = 0 VDC – MINIMUM TURNDOWN ENABLED
1 - 100% = 0 - 10 VDC = FURNACE MODULATION
Heat Pump Heating: The Heater Control % displays internal heating ramp as a
percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Hot Gas Reheat:
If hot gas reheat is staged control:
“Staged reheat is: ON/OFF” will indicate operation.
If hot gas reheat is modulating bypass damper control:
0% = OFF
1% - 100% = 4 - 10 VDC = AIRFLOW DAMPER MODULATION
If hot gas reheat is modulating valve control:
0% = OFF
1% - 100% = 0 - 10 VDC = HOT GAS REHEAT VALVE MODULATION

T

his

screen

indicaTes

elecTric

preheaT

operaTion

. (

if

equipped

)

This screen appears if Electric Preheat frost control was provided.

®