DDC Controller for Tempered Air Products

*The BACnet IP/Eth card is configured for DHCP
from the factory.
To view the current parameters, go the BMS Config
menu within the controller by pressing the

Prg

Esc

key.

To access the BMS
Config
sub-menu, enter
the service password
(Default=1000).

Protocol must be
BACnet IP/Eth and
BACnet Plugin must be
YES.

Press

Prg

Esc

arrow button

to view next screen.
Current BACnet IP
parameters should be
displayed. If values
appear to be zero, follow
the procedure below.
To read current
parameters:
1. Power on controller

and allow several
minutes to initialize.

2. Go to BMS Config

menu and view
BACnet Read/Write
screen.

3. Change Function to

Read

and Update? to

YES

.

Current BACnet IP
parameters should now

be displayed in the BACnet TCP/IP SETUP screen.
If all values appear to be zeros, consult the factory.
(Make sure you have allowed several minutes for the
controller to initialize). *Values may appear to be zero
prior to setting the Function to READ.
To change BACnet TCP/IP parameters:
1. Power on the controller and allow several

minutes to initialize.

2. Go to BMS Config menu and view TCP/IP

SETUP screen.

3. Move cursor to desired parameter by pressing

the

Prg

Esc

Prg

Esc

buttons. Press

Prg

Esc

to select the

parameter to change. Press the

Prg

Esc

Prg

Esc

buttons

to adjust the parameter. Press

Prg

Esc

to save

adjusted value.

4. Once desired parameters have been entered, go

to BACnet Read/Write screen. Change Function
to Write and Update? to YES.

5. Reboot the controller by cycling power to the

unit. Allow several minutes for the controller to
initialize.

BACnet IP/Eth Quick Start

BMS Configuration

Protocol:

BACnet IP/Eth

BACnet Plugin?

YES

TCP/IP SETUP

Instance:

77000

IP set by:

DHCP

IP:

128.1.104.134

Subnet:

255.255.000.000

Gatewy:

128.1.0.12

TCP/IP Setup

DNS 1:

193.168.001.001

DNS 2:

193.168.001.001

Type: IP

BACnet Read/Write

Function:

Read

Update?

Yes

*Cycle unit power to confirm

write command.

G.

Service

c. BMS Config

The communication card
is located in the Serial
Card
port on the face of
the controller. The card
includes two sets of LED
lights for communication
troubleshooting.
Status LED: Indicates the status of communication
between the card and controller.
• Quick green-off-green if communication with

controller is ok.

• Slow red-off-red if communication is not

established.

Ethernet LED: Indicates the status of communication
with the network. Wait for 40 seconds to determine
status of communication.
• Flashing green, communication is OK.
• Steady red, communications is not established.

Communication Troubleshooting
See Carel Data sheet for more info.
If attempting to communicate with the controller over
BACnet IP/Eth, refer to the card LEDs for system
information.
Status LED slow red blink
• Confirm card is firmly plugged in.
• Confirm BMS Protocol is set to BACnet IP/Eth.
Ethernet LED red on
• Confirm card is connected to the network.

Recalling Factory Parameters
Follow this procedure to revert to factory parameters
for one power cycle. When restarted, the card will
resume using the previous user parameters.
Factory Default IP address: 172.016.000.001
1. With controller off, hold the push button located

on the BACnet IP/Eth card, while powering the
controller back on.

2. Continue to hold the button, while watching the

Status LED. Wait for the Status LED to blink red
slowly, and release before the third slow flash.

3. Wait for about one minute for the factory

parameters to be loaded.

4. Follow the procedure to read the current

parameters to confirm factory defaults have been
loaded.

Push Button

Ethernet

LED

Status

LED

MAC address

6. View TCP/IP parameters. If changed values did

not save, contact the factory.

®