On/off unit setpoint, Clock/scheduler input/output, Data logger – Greenheck Microprocessor Controller (474706 IOM) TAP v1.04 June 2011 (ERCH, ERH, APEX, VER, ERT) User Manual

Page 10: Board switch service, Menu overview, Press, Ddc controller for tempered air products

background image

10

DDC Controller for Tempered Air Products

Menu Overview

a. Information

b. Overrides

On/Off Unit

Setpoint

Heater Lockout

Lockout heater when

outside above:

70.0°F

Hysteresis:

2.0°F

Set Point Source

Use local set point,
or BMS interface set

point?

Local

Clock/Scheduler

Input/Output

Hr:Min:Sec

MM/DD/YY

Alarm Description

Room T:

##.#

Discharge T:

##.#

Outside Air T:

##.#

Cold Coil T:

##.#

Unit Status

Data Logger

Board Switch

Unit Address:

1

Switch to unit:

1

1 . . . . . . . . . . 16

17 . . . . . . . . . 32

Board Switch

Service

Unit ON/OFF Control

Enable unit OnOff

By digit input:

Yes

By BMS:

No

By scheduler:

Yes

Room Set Point

Local set pt:

72.0°F

BMS set pt:

###.#°F

Active set pt:

###.#°F

Dehumidification lock

Lockout dehumidific–

action until outside

air is 10.0°F above

cold coil set point.

Scheduler

Number of schedules:

0

Holidays

Holiday = unoccupied mode

for 24 hours.

Number of Holidays:

##

Information

pCO Type: pCO3 Small

Total Flash:

####KB

Ram:

####KB

Built-in type:

T Memory writes:

##

Main Cycle:

7.4 Cycle/s

###ms

Control Loop Overrides

Unit must be ON.
To resume normal

operation, cycle unit

power.

HotGas Reheat Override

Hot Gas Reheat

Loop Control:

Auto

Reheat:

100%

On/Off Unit

Actual state:

Off by DIG INPUT (ID4)

Change to:

SWITCH ON

*Power ID4 to start…

Supply Set Point

is currently =

60°F

This set pt is reset up/down

by the DDC.

Cooling Lockout

Lockout cooling when

outside below:

55.0°F

Hysteresis:

2.0°F

Clock

Day:

Monday

Date:

MM/DD/YY

Hour:

##:##

Analog Input

Outside Temperature

Input B01:

###.#°F

Digital Input

Supply Fan
DI 1 Status:

(Closed)

(Open)

Relay Output

Defrost
Relay 1 Status:

(Off)

(On)

Analog Output Y1

Wheel
Output:

##.#vdc

Information

Greenheck Fan Corp.

Code: XXXXXXXXX00

Ver.: 1.04

##/##/##

Manual/IOM:

474706

Bios:

5.12 ##/##/##

Boot:

4.03 ##/##/##

Heating Override

Heating Control:

Auto

Heating:

100%

Service Password

Insert service
password (PW1):

0000

Supply Reset Limits

Supply Min:

55.0°F

Supply Max:

90.0°F

Economizer Lockout

Lockout econo when

outside below:

40.0°F

Hysteresis

2.0°F

Scheduler

Schedule #:

#

Time On:

##:##

Time Off:

##:##

Days Enabled:

MTWTFSS

Analog Input

Outside Temperature

Manual Control B01:

OFF

Manual Position

#

Value

###.#°F

Supply Air Reset

Outside:

Supply

60.0°F - - >

72.0°F

70.0°F - - >

55.0°F

Supply air low limit

Alarm when supply is

below:

35.0°F

Alarm delay:

300s

Holiday #1

Month:

MM

Day:

DD

Unoccupied for 24 hrs

Energy Wheel Override

Wheel Control:

Auto

Wheel:

Off

Digital Input

Supply Fan sw
Manual DI 1:

OFF

Manual Position: CLOSED
DI 1 Status: Open

Supply Set From BMS

BMS interface:

aaa.a°F

Set pt min:

55.5°F

Set pt max:

90.0°F

Defrost

Allow wheel defrost

mode when outside

is below:

5.0°F

Wheel Preheat Override

Energy Recovery Wheel
Preheat Control:

Auto

Preheater:

Off

Relay Output

Defrost
Manual Relay 1:

OFF

Manual Position:

OFF

Relay 1 Status:

OFF

Cold Coil Set Point

Normal Mode:

55.0°F

Dehumidify:

50.0°F

Active set pt:

55.0°F

UnOcc Fan Cycle Setup

Unit will energize to maintain

unocc room set points.

Heating:

65.0°F

Cooling:

80.0°F

Differential:

5.0°F

Cooling Override

Cooling Control:

Auto

Cooling:

100%

Analog Output Y1

Wheel
Mode:

Auto

Manual Value: 0.0vdc
Output:

0.0vdc

All I/O points are included. An example of each is shown.

Press

Prg

Esc

to enter menus.

I/O Manual Management

END OF OVERRIDE MENU

Press ENTER to go to

I/O Manual Management

menu.

®