On/off unit setpoint, Clock/scheduler input/output, Data logger – Greenheck Microprocessor Controller (474706 IOM) TAP v1.04 June 2011 (ERCH, ERH, APEX, VER, ERT) User Manual
Page 10: Board switch service, Menu overview, Press, Ddc controller for tempered air products

10
DDC Controller for Tempered Air Products
Menu Overview
a. Information
b. Overrides
On/Off Unit
Setpoint
Heater Lockout
Lockout heater when
outside above:
70.0°F
Hysteresis:
2.0°F
Set Point Source
Use local set point,
or BMS interface set
point?
Local
Clock/Scheduler
Input/Output
Hr:Min:Sec
MM/DD/YY
Alarm Description
Room T:
##.#
Discharge T:
##.#
Outside Air T:
##.#
Cold Coil T:
##.#
Unit Status
Data Logger
Board Switch
Unit Address:
1
Switch to unit:
1
1 . . . . . . . . . . 16
17 . . . . . . . . . 32
Board Switch
Service
Unit ON/OFF Control
Enable unit OnOff
By digit input:
Yes
By BMS:
No
By scheduler:
Yes
Room Set Point
Local set pt:
72.0°F
BMS set pt:
###.#°F
Active set pt:
###.#°F
Dehumidification lock
Lockout dehumidific–
action until outside
air is 10.0°F above
cold coil set point.
Scheduler
Number of schedules:
0
Holidays
Holiday = unoccupied mode
for 24 hours.
Number of Holidays:
##
Information
pCO Type: pCO3 Small
Total Flash:
####KB
Ram:
####KB
Built-in type:
T Memory writes:
##
Main Cycle:
7.4 Cycle/s
###ms
Control Loop Overrides
Unit must be ON.
To resume normal
operation, cycle unit
power.
HotGas Reheat Override
Hot Gas Reheat
Loop Control:
Auto
Reheat:
100%
On/Off Unit
Actual state:
Off by DIG INPUT (ID4)
Change to:
SWITCH ON
*Power ID4 to start…
Supply Set Point
is currently =
60°F
This set pt is reset up/down
by the DDC.
Cooling Lockout
Lockout cooling when
outside below:
55.0°F
Hysteresis:
2.0°F
Clock
Day:
Monday
Date:
MM/DD/YY
Hour:
##:##
Analog Input
Outside Temperature
Input B01:
###.#°F
Digital Input
Supply Fan
DI 1 Status:
(Closed)
(Open)
Relay Output
Defrost
Relay 1 Status:
(Off)
(On)
Analog Output Y1
Wheel
Output:
##.#vdc
Information
Greenheck Fan Corp.
Code: XXXXXXXXX00
Ver.: 1.04
##/##/##
Manual/IOM:
474706
Bios:
5.12 ##/##/##
Boot:
4.03 ##/##/##
Heating Override
Heating Control:
Auto
Heating:
100%
Service Password
Insert service
password (PW1):
0000
Supply Reset Limits
Supply Min:
55.0°F
Supply Max:
90.0°F
Economizer Lockout
Lockout econo when
outside below:
40.0°F
Hysteresis
2.0°F
Scheduler
Schedule #:
#
Time On:
##:##
Time Off:
##:##
Days Enabled:
MTWTFSS
Analog Input
Outside Temperature
Manual Control B01:
OFF
Manual Position
#
Value
###.#°F
Supply Air Reset
Outside:
Supply
60.0°F - - >
72.0°F
70.0°F - - >
55.0°F
Supply air low limit
Alarm when supply is
below:
35.0°F
Alarm delay:
300s
Holiday #1
Month:
MM
Day:
DD
Unoccupied for 24 hrs
Energy Wheel Override
Wheel Control:
Auto
Wheel:
Off
Digital Input
Supply Fan sw
Manual DI 1:
OFF
Manual Position: CLOSED
DI 1 Status: Open
Supply Set From BMS
BMS interface:
aaa.a°F
Set pt min:
55.5°F
Set pt max:
90.0°F
Defrost
Allow wheel defrost
mode when outside
is below:
5.0°F
Wheel Preheat Override
Energy Recovery Wheel
Preheat Control:
Auto
Preheater:
Off
Relay Output
Defrost
Manual Relay 1:
OFF
Manual Position:
OFF
Relay 1 Status:
OFF
Cold Coil Set Point
Normal Mode:
55.0°F
Dehumidify:
50.0°F
Active set pt:
55.0°F
UnOcc Fan Cycle Setup
Unit will energize to maintain
unocc room set points.
Heating:
65.0°F
Cooling:
80.0°F
Differential:
5.0°F
Cooling Override
Cooling Control:
Auto
Cooling:
100%
Analog Output Y1
Wheel
Mode:
Auto
Manual Value: 0.0vdc
Output:
0.0vdc
All I/O points are included. An example of each is shown.
Press
Prg
Esc
to enter menus.
I/O Manual Management
END OF OVERRIDE MENU
Press ENTER to go to
I/O Manual Management
menu.
®