DDC Controller for Tempered Air Products

T

his

screen

allows

The

adjusTmenT

of

parameTers

for

The

economizer

funcTion

.

This screen only appears if an economizer mode was selected with the unit.

The controller utilizes a PI loop control for the economizer function. This
allows for less sporadic changes in supply temperature, resulting in a smooth
reaction to changing conditions. To speed up reaction time, decrease the
integration time. For slower reaction time, increase the integration time. When
making adjustments, make them in small increments and test the system to
determine if the new setting is adequate prior to further adjustment. The band
is the range that the integration will occur between. Range of integration =
Supply set point ± Band.
The minimum ON and OFF times prevent the energy wheel from short cycling
during economizer mode.

T

his

screen

displays

The

digiTal

scroll

compressor

parameTers

.

This screen only appears if a digital scroll compressor was provided with the unit.

Minimum OFF: This is the minimum voltage the controller outputs when the

digital scroll is disabled/OFF

Minimum ON: This is the minimum voltage the controller outputs when the

digital scroll is enabled/ON.

Maximum: This is the maximum voltage the controller outputs when the digital

scroll is operating at full capacity.

Delay OFF: Delays shutting off digital scroll by this duration.
Max Power Start: Upon starting, the digital scroll will run at full capacity for

this duration. This ensures the refrigeration system is at
proper conditions, prior to modulation.

T

his

screen

displays

The

number

of

sTandard

compressor

sTages

provided

wiTh

The

uniT

and

shows

The

roTaTion

sequence

.

This screen only appears if DX cooling was provided with the unit.

The number of stages displayed is equal to the number of non-modulating
compressors. Factory default compressor rotation is LIFO (Last In, First Out).
Compressor rotation can not be changed on units equipped with: Digital
Scrolls, Hot Gas Reheat or Heat Pump.

T

his

screen

allows

adjusTmenT

of

The

c

ooling

pi

conTrol

loop

.

This screen only appears if cooling option was provided with the unit.

The controller utilizes a PI loop control for cooling. This allows for less
sporadic changes in supply temperature, resulting in a smooth reaction to
changing conditions. To speed up reaction time, decrease the integration
time. For slower reaction time, increase the integration time. When making
adjustments, make them in small increments and test the system to determine
if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.

T

his

screen

allows

The

adjusTmenT

The

T

imed

e

xhausT

f

rosT

c

onTrol

on/off

Times

.

This screen only appears if Timed Exhaust Frost Control was provided with the unit.

The ON/OFF times prevent the build up of frost when the unit is in Timed
Exhaust Frost Control mode.

The Factory Settings menu allows adjustment of parameters that are critical for
proper unit operation. Adjustment of these parameters is only recommended with
factory guidance. To access the Factory Settings menu, enter the manufacturer
password (Default=1000).

Economizer Controller

Integration

300s

Band:

20°F

Econo ON/OFF times:

Minimum ON:

300s

Minimum OFF:

300s

Supply Fan Cycling

Defrost setup

Fan off time:

5min

Fan on time:

30min

Cooling Controller

Integration:

300s

Band:

20°F

Compressor Setup

# of stages:

2

Rotation:

LIFO

Digital Compressor

Minimum OFF:

1.0vdc

Minimum ON:

1.9vdc

Maximum:

5.0vdc

Delay OFF:

60s

Max Power Start:

120s

H.

Manufacturer

c. Factory Settings

®