24

DDC Controller for Tempered Air Products

T

his

screen

allows

adjusTmenT

of

The

fan

airflow

proving

swiTch

Time

delay

.

Since the unit is only part of a complete system, the airflow(s) may momentarily
change (ie. If a downstream damper closes). This delay is intended to prevent
false loss of airflow alarms. (Factory Default = 30 seconds)

T

his

screen

allows

adjusTmenT

of

The

fan

sTarT

delay

.

This timer allows the damper time to open before the fan start sequence
begins. This prevents the fans from having to overcome higher static pressure
when the damper(s) are opening. (Factory Default = 10 seconds)

T

his

screen

allows

adjusTmenT

of

The

delay

beTween

heaT

and

cool

modes

.

This time delay prevents short cycling between heating, cooling and/or
economizer modes.

T

his

screen

displays

whaT

The

uniT

will

do

in

unoccupied

mode

.

Setting the Type to CycleSupplyFan will engage the unit to maintain space
temperature. However, a room temperature sensor must be wired between
controller terminals B4 and BC4. If desired, the Source offers three options to
control occupancy. The factory default is terminal ID6 on the controller.
Input ID6: Typically used with a remote time clock, motion sensor or switch

(default).

BMS: BMS control (see Points List). BMS can be overridden with ID6.
Time Clock: Internal time clock (Scheduler). See Clock/Scheduler menu for

more information. The Scheduler can be overridden with digital
input ID6.

Without the room temperature sensor, the Type will be Unit Off, forcing the unit
off during unoccupied mode.

T

his

screen

allows

adjusTmenT

of

The

s

upply

r

eseT

pi

conTrol

loop

,

for

r

oom

T

emp

c

onTrol

.

This screen only appears if a Room Temp Sensor is wired to controller terminals
B4 and BC4.

The controller utilizes a PI loop control for supply reset based on room temp.
This allows for less sporadic changes in supply air temperature, resulting in a
smooth reaction to changing conditions. To speed up reaction time, decrease
the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments and test the system
to determine if the new setting is adequate prior to further adjustment. The
band is the range that the integration will occur between.

Mod Hot Gas Setup

Minimum ON:

4.0vdc

Maximum ON:

10.0vdc

Supply Reset Control

Integration:

1200s

Band:

10°F

Heat/Cool Delay

Time delay between heating,

cooling &/or economizer

modes. Delay:

180s

Unoccupied Mode Setup

Type:

CycleSupplyFan

Source:

Input ID6

Damper Setup

Allow the dampers to open

for: 10 seconds before

starting the fans.

Fan/Airflow Proving

Alarm delay:

30s

(inputs ID1 & ID5)

T

his

screen

allows

adjusTmenT

of

The

hoT

gas

flush

sysTem

.

This screen appears if hot gas reheat with flush was provided (except heat pump).

The hot gas flush cycle is designed to provide a momentary flush of the hot
gas reheat system. This prevents the build up of oil in the reheat coil. The
flush sequence starts by fully opening the reheat valve for a period of Duration
(Factory Default = 1 minute). Once the flush duration is complete, the valve
resumes modulation for a period of Cycle (Factory Default = 30 minutes).

T

his

screen

allows

adjusTmenT

of

The

hoT

gas

reheaT

bypass

damper

.

This screen appears if modulating hot gas reheat was provided.

Hot Gas Flush Setup

Cycle:

30minutes

Duration:

1minutes

®