DDC Controller for Tempered Air Products

The pCOe is an Auxiliary I/O module that can be
used to monitor additional statuses within the unit.
The pCOe allows the user to view:
• 4 Digital Inputs
• 4 Digital Outputs
• 4 Analog Inputs
• 1 Analog Output

The inputs can be monitored either via the controller display or
Building Management System. See Points List for detailed point
information.

In order for the main controller to read the Auxiliary I/O, several parameters must be set in the menu screens. (If
you have a pCOe installed from the factory, the controller is most likely already set up for communication with
the main controller.)

Enable Expansion I/O - Go to Manufacturer > Configuration. You will have to
enter the Manufacturer password (Default = 1000). Go to the Unit Expansion
I/O screen, and make sure Enable Expansion = Yes.

View Input Values - To view input values, go to Input/Output. At the very end
of the menu are the status screens of the pCOe inputs and outputs. Similarly,
the pCOe I/O values can be viewed on the BMS. See Points List for more
details.

Customize Analog Inputs - The analog inputs are grouped in pairs according
to their input types (Channels B1, B2 and Channels B3, B4). To select the
input type, go to Manufacturer > I/O Configuration. You will have to enter the
Manufacturer password (Default = 1000). At the very end of the menu are the
I/O Config screens for the pCOe analog inputs.
The pCOe analog inputs are set up as Carel NTC temperature probes default
from the factory. The analog inputs can be also be set for the following input
types: 0/1VDC, 0/20mA, 4/20mA or 0/5VDC.
If selected as anything other than Carel NTC, the user has the capability to
scale the input to match the probe range. An example screen is shown on the
left.

Auxiliary I/O (pCOe)

Setup

Unit Expansion I/O

Enable Expansion

Yes

pCOe I/O Config

pCOe number:

1

Analog input type
Ch 1&2 : 4.. 20 mA
Ch 3&4 : Carel NTC

pCOe I/O Config

pCOe number:

1

Analog input limits

Ch 1 Min:

0.0

Ch 1 Max:

10.0

Ch 2 Min:

0.0

Ch 2 Max:

10.0

pCOe Digital Inputs

pCOe number:

1

Channel ID1:

Open

Channel ID2:

Open

Channel ID3:

Open

Channel ID4:

Open

pCOe Digital Outputs

pCOe number:

1

Output NO1:

OFF

Output NO2:

OFF

Output NO3:

OFF

Output NO4:

OFF

pCOe Analog Channels

pCOe number:

1

Input B1:

0.0

Input B2:

0.0

Input B3:

70.0°F

Input B4:

70.0°F

Output Y1:

0.0vdc

Digital

Outputs

24 VAC Power

0/10 VDC

Analog Output

Communication

Cable to Main

Controller

Digital Inputs

Linked Analog Inputs

(NTC, 0/1VDC, 0/20mA, 4/20mA, 0/5VDC)

Linked Analog Inputs

(NTC, 0/1VDC, 0/20mA, 4/20mA, 0/5VDC)

®