DDC Controller for Tempered Air Products

The DDC controller will revert to a default main menu loop. This loop includes several screens to view the
operating conditions of the unit. Scroll through the menu screens by using the

Prg

Esc

Prg

Esc

keys. Screens with a

dashed line border are dependent upon an optional accessory and may not always appear.

T

he

iniTial

menu

screen

displays

The

program

version

,

uniT

code

and

s

TaTus

l

ine

. T

he

s

TaTus

l

ine

displays

which

mode

The

uniT

is

in

.

Possible modes include:

• Initial Delay

• Sys On-Dehumidifying

• Opening Dampers

• Sys On-Dehumid & Reheat

• Exhaust Fan Starting

• Unoccupied-Unit Off

• Supply Fan Starting

• Unoccupied-Heating

• System On

• Unoccupied-Cooling

• Defrost Mode Active

• Manual Override

• Sys On-Economizer

• Remote Off

• Sys On-Heating

• Press Alarm Button!!!

• Sys On-Cooling

T

he

TemperaTures

on

This

screen

display

real

Time

condiTions

from

The

sensors

locaTed

in

The

uniT

and

The

room

(

if

insTalled

).

e

nergy

r

ecovery

w

heel

s

TaTus

. (

if

equipped

)

If equipped with an energy wheel, this screen will display the wheel speed. If
the unit contains a wheel VFD, this screen will display the wheel speed being
sent via the controller’s wheel analog output.
If the unit does not contain an energy wheel VFD, 0% = OFF; 100% = ON.
If equipped with a frost control method, this screen will also display wheel
pressure differential status. A pressure status of high is an indication of frost
accumulation.

c

ooling

sTaTus

is

displayed

,

along

wiTh

compressor

operaTion

. (

if

equipped

)

This screen appears if a cooling option is provided.

Chilled Water: The Cooling Control % is directly proportional to the 0-10 VDC
output signal.
0% Cooling = 0 VDC

100% Cooling = 10 VDC

The cooling control output can be configured to DIRECT / REVERSE acting,
along with the minimum and maximum output voltages by entering the
MANUFACTURER menu.
Packaged DX Cooling: The Cooling Control displays internal cooling ramp as
a percent. Compressor operation is displayed when engaged.
• D = Digital Scroll Compressor Operation
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Heat Pump Cooling: The Cooling Control displays internal cooling ramp as a
percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation

Main Menu Overview

TIME DATE UNIT##

TAP v1.04 GMYXX000X00

STATUS LINE

TIME DATE UNIT##

Supply Air:

000.0°F

Outside Air: 000.0°F

Cold Coil:

000.0°F

Room:

000.0°F

STATUS LINE

Energy Recovery

Wheel:

000% Speed

Wheel Differential

Pressure Is:

Normal

STATUS LINE

Cooling Status

Cooling Control:

000%

Compressor

D 1 2

STATUS LINE

®

®