beautypg.com

Controller overview, Ser vic e car d, Field car d ser ial car d – Greenheck Microprocessor Controller (474706 IOM) TAP v1.04 June 2011 (ERCH, ERH, APEX, VER, ERT) User Manual

Page 5

background image

5

DDC Controller for Tempered Air Products

Controller Overview

J1J1

J24J24

J14J14

J11J11

J15J15

J2J2

J5J5

J4J4

J3J3

ser
vic
e car

d

Rx-/Tx-

Rx+/Tx+

GND

C1

NO1

NO2

NO3

C1

C4

NO4

NO5

NO6

C4

C7

NO7

C7

NO8

C8

NC8

G

G0

24 VAC to Controller

B1

B2

B3

GND

+VDC

+Vterm

GND

+5 VREF

B4

BC4

B5

BC5

VG

VG0

Y1

Y2

Y3

Y4

ID1

ID2

ID3

ID4

ID5

ID6

ID7

ID8

IDC1

J10

J9

field car

d

ser
ial car

d

input: 24

V ~ / ; 50 t

o 60 H

z

max. po

w

er

: 40
VA/15W

J12J12

J13J13

Outdoor Air Intake Temperature Sensor

Supply Discharge Temperature Sensor

After Cold Coil Temperature Sensor

Sensor B1, B2, B3 Commons

Room Temperature Sensor

Call for Dehumidification

24 VAC for Analog Outputs

24 VAC When Unit On
Frost Control Enable
Output to Supply Fan
Output to Exhaust Fan

24 VAC from Supply Fan Proving
Heating Enable/Reversing Valve
Compressor Output 1
Compressor Output 2

24 VAC
Output to Dampers

Alarm Dry Contact

Energy Wheel Analog Output

Heating Analog Output

Cooling Analog Output

Hot Gas Reheat Analog Output

Supply Fan Proving

Wheel Pressure

Wheel Rotation Alarm

Unit On/Off

Exhaust Fan Proving

Occupied/Unoccupied Input

Dirty Filter

Compressor Limit

BACnet, LonWorks and Modbus cards
are located in Serial Card port

DDC Remote Display

(straight six wire phone cable)

®