DDC Controller for Tempered Air Products

Examples of Alarms

If an alarm occurs, the

Prg

Esc

button will glow red on the controller and the remote display (if installed).

To view alarm, press the

Prg

Esc

button once. This will display the most recent

alarm. Press the

Prg

Esc

button again to reset the alarm. If the alarm cannot be

cleared, the cause of the alarm has not been fixed. Press the

Prg

Esc

Prg

Esc

buttons to

view any additional occurring alarms.

This is an example of an outdoor air sensor failure.

This screen appears if there are no active alarms.

To view all saved alarms, press the

Prg

Esc

button to enter the DATA LOGGER. For

more information, see the Data Logger menu.

Examples of Alarms

Outdoor Air Temperature
Sensor Failure

Failure of outside air temperature sensor.

Alarm only

Supply Air Temperature
Sensor Failure

Failure of supply air temperature sensor.

Alarm & Shutdown

Cold Coil Temperature
Sensor Failure

Failure of after cooling coil air temperature sensor.

Alarm only

Room Temperature
Sensor Failure

Failure of room temperature sensor.
(If UnOccupied - Cycle On Room is enabled)

Alarm only

System has exceeded the
set number of run hours

The unit has been operating for a period longer than
the maintenance set point.

Alarm only

Supply airflow

Indicates a loss of airflow in the supply fan.

Alarm & Shutdown

Wheel Pressure - Dirty
Wheel/High CFM

Indicates a buildup of pressure across the energy
wheel.

Alarm only

Energy recovery wheel
rotation. Check wheel.

Indicates a wheel rotation failure.

Alarm only

Exhaust Airflow

Indicates a loss of airflow in the exhaust fan.

Alarm & Shutdown

Filter Alarm

Indicates a buildup of pressure across the filters.

Alarm only

A compressor limit
switch has tripped

Indicates a high or low refrigerant pressure switch
has tripped.

Alarm only

Supply temperature low
limit alarm

Indicates a supply air temperature lower than the
supply low limit set point.

Alarm & Shutdown

pCOe Offline

Indicates communication with pCOe auxiliary I/O has
failed.

Alarm only

pCOe - Analog input
probe on channel #
disconnected or broken

Indicates an analog probe failure on the pCOe.
Check integrity of auxiliary I/O analog probes.

Alarm only

Alarms

Press DOWN to review

current alarm(s).
Press ESC to exit.
Press ALARM to reset.

Alarms

No active alarm

Press ENTER

to DATA LOGGER

Outside Air Temperature

Sensor B01 Failure

®