Greenheck Microprocessor Controller (474706 IOM) TAP v1.04 June 2011 (ERCH, ERH, APEX, VER, ERT) User Manual

Page 14

background image

14

DDC Controller for Tempered Air Products

u

sers

can

choose

eiTher

The

conTroller

or

The

bms

To

deTermine

s

upply

a

ir

s

eT

p

oinT

during

operaTion

.

This screen only appears if the controller was supplied with BMS capability.

Local means the controller set point will be used during operation. (Outdoor Air
Reset or Room Reset)
BMS means that the BMS set point will be used during operation.

T

his

screen

displays

The

room

seT

poinTs

for

heaTing

and

cooling

operaTion

during

unoccupied

mode

.

This screen only appears if the unoccupied mode is set to “Cycle on Room”
instead of “Unit Off”. A room temp sensor must be wired into the controller. For
energy recovery units, a Night Set-Back Damper must be installed.

In unoccupied mode when the temperature falls below the room Heating set
point, the supply fan and heating will turn on. If the unit is an Energy Recovery
unit, the Night Set-Back Damper will also open. The unit will discharge the
Supply Max temperature per the Supply Reset Limits screen, until the room
set point is satisfied. Unit will then shut down. When the temperature rises
above the Cooling set point, the unit will discharge the Supply Min temperature
per the Supply Reset Limits screen until the room temperature set point is
satisfied. Unit will then shut down.
The differential acts as a hysteresis to keep the heating and cooling from
cycling too often. For example, on a call for heating, the unit turns on at 60°F
and turns off at 65°F. For cooling, the unit turns on at 85°F and turns off at 80°F.

T

his

screen

displays

The

TemperaTure

aT

which

The

uniT

will

enable

frosT

conTrol

mode

if

necessary

. (f

acTory

d

efaulT

= 5°f)

This screen only appears if the unit has an energy recovery wheel and a frost
control method was provided with the unit.

Upon sensing a high differential pressure across the energy wheel, the unit will
go into defrost if the outside air temperature is below this temperature setting.

T

his

screen

displays

The

low

supply

air

TemperaTure

limiT

.

If the unit supply air temperature falls below Supply Air Low Limit for a period
of Alarm Delay, the unit will shut down and an alarm will be signaled. The
purpose of the supply low limit is to protect the building and contents from
cold supply air. It is NOT designed to protect the air-handling unit.
If the unit does not have chilled water (CW) or hot water (HW) coils, it should
not need additional protection from freezing. If the unit does have CW or HW
coils, field provided coil freeze protection may be necessary.

e

conomizer

lockouT

prevenTs

The

uniT

from

going

inTo

economizer

mode

when

The

ouTdoor

air

condiTions

are

Too

cold

.

This screen only appears if economizer was provided with the unit.

The lockout prevents outdoor air from: (1) entering the space at too cold of a
temperature or (2) entering heating or cooling coils at conditions that could
freeze the coils. Built-in hysteresis of 2°F. The hysteresis is similar to a dead-
band above and below the lockout set point. Example: If Lockout = 40°F,
economizer is locked out below 38°F and enabled above 42°F outside air
temperature.)

T

his

screen

displays

The

TemperaTure

difference

aT

which

The

dehumidificaTion

mode

is

locked

ouT

. (f

acTory

d

efaulT

= 10°f)

This screen only appears if the unit is equipped with cooling.

This setting prevents the unit from operating in dehumidification mode when the
outdoor air conditions are relatively cool. Example: If the cold coil set point is
55°F, dehumidification mode cannot operate until the outdoor air is at least 65°F.

Dehumidification lock

Lockout dehumidification until

outside air is 10.0°F above

cold coil set point.

Economizer Lockout

Lockout econo when outside

below:

40.0°F

Hysteresis

2.0°F

Supply air low limit

Alarm when supply is

below:

35.0°F

Alarm delay:

300s

Set Point Source

Use local set point, or BMS

interface set point? Local

Defrost

Allow wheel defrost

mode when outside

is below:

05.0°F

UnOcc Fan Cycle Setup

Unit will energize to maintain

unocc room set points.

Heating:

65.0°F

Cooling:

80.0°F

Differential:

5.0°F

®