DDC Controller for Tempered Air Products

T

his

screen

displays

The

compressor

minimum

on

and

off

Times

.

This screen only appears if DX cooling was provided with the unit.

The compressor minimum ON/OFF times prevents short cycling of the
compressors.

T

his

screen

allows

adjusTmenT

of

The

minimum

on/off

Times

for

The

hoT

gas

reheaT

coil

.

This screen appears if ON/OFF hot gas reheat was provided with the unit.

This is the minimum on/off time operation for the hot gas reheat coil. The
minimum run time prevents short cycling of the coil, allowing for better oil
distribution through the DX system. CONSULT THE FACTORY BEFORE
CHANGING MINIMUM ON/OFF HOT GAS REHEAT TIMES.

T

his

screen

allows

adjusTmenT

of

The

h

oT

g

as

r

eheaT

pi

conTrol

loop

.

This screen only appears if hot gas reheat was provided with the unit.

The controller utilizes a PI loop control for reheat. This allows for less sporadic
changes in supply air temperature, resulting in a smooth reaction to changing
conditions. To speed up reaction time, decrease the integration time. For
slower reaction time, increase the integration time. When making adjustments,
make them in small increments and test the system to determine if the new
setting is adequate prior to further adjustment. The band is the range that the
integration will occur between.

T

his

screen

allows

The

user

To

enable

The

heaTer

To

provide

reheaT

in

addiTion

To

hoT

gas

reheaT

This screen appears if hot gas reheat and a heating option was provided (except
heat pump).

Setting the heater parameter to enable allows the heating option to provide
additional reheat beyond what the hot gas reheat can provide. This would
typically only be used if the supply air temperature is too cold.

T

his

screen

allows

The

user

To

enable

The

heaTer

for

reheaT

purposes

.

This screen appears if a heating option was provided and the unit does NOT have
hot gas reheat OR a heat pump.

If it is desired that the heater be used to reheat the air off of the cooling coil when
in dehumidification, adjust this screen so the heater is ENABLED for reheat.

T

his

screen

allows

adjusTmenT

of

The

h

eaTing

pi

conTrol

loop

.

This screen only appears if heating option was provided with the unit.

The controller utilizes a PI loop control for heating. This allows for less
sporadic changes in supply temperature, resulting in a smooth reaction to
changing conditions. To speed up reaction time, decrease the integration
time. For slower reaction time, increase the integration time. When making
adjustments, make them in small increments and test the system to determine
if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.

T

his

screen

displays

when

each

compressor

in

a

single

or

dual

sTage

dx

uniT

will

engage

/

disengage

.

This screen only appears if DX cooling was provided with the unit.

Each compressor will engage and disengage based upon the percentage of
cooling capacity the controller needs.

Compressor Timers

Minimum ON:

30s

Minimum OFF:

180s

Between Stages:

30s

Compressor Staging

Stage1: ON @ 50% OFF 0%

Stage2: ON @ 100% OFF 50%

Heater Controller

Integration:

300s

Band:

20°F

Reheat Setup

Will heater be used for reheat

during dehumidification?

Reheat:

Disable

Reheat Setup 2

Will heater be used for reheat

along with hot gas?

Heater:

Disable

Hot Gas Controller

Integration:

300s

Band:

20°F

Hot Gas Setup

Hot gas reheat coil minimum

on/off time:

10minutes

®