DDC Controller for Tempered Air Products

The Overrides menu is for start-up, commissioning and troubleshooting.
This menu allows the user to override the control loops. If further control is
required, the user can also manually control the controller inputs and outputs.
To access the Overrides sub-menu, enter the service password (Default=1000).

To manually override a control loop, the unit must be ON. In each respective
screen, change the control from AUTO to MANUAL.
To resume normal operation after overriding the controller, simply cycle power
to the unit.

T

his

screen

allows

The

user

To

override

The

energy

wheel

operaTion

.

This screen only appears if the unit is equipped with a non-VFD operated energy
wheel.

When the Wheel Control is in the MANUAL mode, use the arrow buttons to turn
the wheel ON or OFF.

T

his

screen

allows

The

user

To

override

The

energy

wheel

operaTion

.

This screen only appears if the unit is equipped with a VFD operated energy wheel.

When the Wheel Control is in the MANUAL mode, use the arrow buttons to
alter the wheel %. This is directly proportional to a 0 - 10 VDC signal being sent
to the energy wheel VFD.

F.

Board Switch

The Board Switch menu allows the user to jump between different controllers
with a remote display. This requires a remote display, along with additional
controllers, set-up in a pLAN network. A pLAN can consist of up to 32 devices, in
different combinations, but a maximum of 31 controllers.

w

hen

viewing

This

screen

from

a

remoTe

display

,

The

user

is

able

To

change

which

conTroller

s

menu

should

be

displayed

.

Unit Address: The pLAN address of the controller the display is currently
accessing.
Switch to unit: The pLAN address of the controller the display would like to
access.

Board Switch

Unit Address:

1

Switch to unit:

1

1 . . . . . . . . . . 16

17 . . . . . . . . . 32

G.

Service

e

nTering

The

i

nformaTion

sub

-

menu

will

display

informaTion

abouT

The

conTroller

and

The

program

loaded

on

The

conTroller

.

Code: Controller setup code determines functionality of program. When
contacting the factory, please reference this code.

The Service menu allows the user to access several sub-menus regarding
controller information, controller overrides, operating hours, BMS configuration,
I/O manual management and Probe Adjustment. The user can also change the
default Service Password (1000) by accessing the Service Settings sub-menu.
By accessing the BMS Config sub-menu, the user can adjust BMS protocol
settings (BACnet, LonWorks, Modbus).

Information

Greenheck Fan Corp.

Code: GMY10000X00

Ver.: 1.04

06/13/11

Manual:

474706

Bios:

5.12 11/17/10

Boot:

4.03 07/03/06

Control Loop Overrides

Unit must be ON.
To resume normal operation,

cycle unit power.

Energy Wheel Override

Wheel Control:

Auto

Wheel:

OFF

Energy Wheel Override

Wheel Control:

Auto

Wheel:

100%

G.

Service

a. Information

G.

Service

b. Overrides

®