beautypg.com

Greenheck Microprocessor Controller (474706 IOM) TAP v1.04 June 2011 (ERCH, ERH, APEX, VER, ERT) User Manual

Page 13

background image

13

DDC Controller for Tempered Air Products

T

his

screen

displays

The

minimum

and

maximum

supply

air

TemperaTure

limiTs

.

This screen only appears if the unit is connected to a room temperature sensor.

The supply air temperature will be controlled within the Supply Min and Supply
Max limits to maintain room temperature set point.

T

hese

parameTers

dicTaTe

The

operaTion

of

The

ouTdoor

air

reseT

funcTion

.

This screen does not appear when a room temp sensor is wired to the controller.

The controller monitors the outdoor air temperature and adjusts the desired
supply temperature accordingly. For example, when the outdoor air is below
60°F, the controller will change the Supply set point to 72°F. If the outdoor
air is above 70°F, the controller will change the Supply set point to 55°F. If
the outdoor air temperature is between 60°F and 70°F, the Supply set point
changes according to the outdoor air reset function. A visual representation of
the outdoor air reset function is shown below.

T

his

screen

displays

The

supply

air

seT

poinT

as

seT

by

a

bms.

This screen appears if the unit has BMS communications and set point source is
set to BMS.

See Set Point Source screen in this menu to allow BMS to determine set point.

T

he

conTroller

will

lockouT

cooling

when

The

ouTdoor

air

TemperaTure

is

below

The

cooling

lockouT

seT

poinT

. (f

acTory

d

efaulT

= 55°f)

This screen only appears if the unit the unit is equipped with cooling.

There is a built in hysteresis of 2°F which prevents the cooling from short
cycling. The hysteresis is similar to a dead-band above and below the lockout
set point. (Example: If Lockout = 55°F, cooling is locked out below 53°F and
enabled above 57°F outside air temperature.)

T

he

conTroller

will

lockouT

heaTing

when

The

ouTdoor

air

TemperaTure

is

above

The

heaTing

lockouT

seT

poinT

. (f

acTory

d

efaulT

= 70°f)

This screen only appears if the unit the unit is equipped with heating.

There is a built in hysteresis of 2°F which prevents the heating from short
cycling. The hysteresis is similar to a dead-band above and below the lockout
set point. (Example: If Lockout = 70°F, heating is locked out above 72°F and
enabled below 68°F outside air temperature.)

T

his

screen

displays

The

TemperaTure

seT

poinTs

for

The

cooling

coil

.

This screen only appears if the unit is equipped with cooling.

The Normal mode set point is the after coil temperature the unit will maintain
under standard operation, when in cooling. If a humidistat was provided
with the unit, the Dehumidify set point is the temperature the cooling coil will
discharge on a call for dehumidification. The Active set point is the cooling coil
discharge temperature the unit is currently trying to maintain.

Supply Reset Limits

Supply Min:

55.0°F

Supply Max:

90.0°F

Supply Air Reset

Outside:

Supply

60.0°F - - >

72.0°F

70.0°F - - >

55.0°F

Supply Set From BMS

BMS interface:

##.#°F

Set pt min:

55.5°F

Set pt max:

90.0°F

Cold Coil Set Point

Normal Mode:

55.0°F

Dehumidify:

50.0°F

Active set pt:

55.0°F

Heater Lockout

Lockout heater when outside

above:

70.0°F

Hysteresis:

2.0°F

Cooling Lockout

Lockout cooling when outside

below:

55.0°F

Hysteresis:

2.0°F

Outdoor Air Reset Function

49°

55°

61°

67°

73°

55°

60°

65°

70°

75°

Outside Air Temperature (°F)

Supply Air Set Point

F)

®