beautypg.com

Gasboy CFN Series SCII Installation Manual User Manual

Page 55

background image

CFN Series System

4-6

05/28/03

TOKHEIM 162 INTERFACE

Electronic Interface

Basic System

1 to 8 Hoses

System consists of one Site Controller II, one computer module, and one C05578
cable and Tokheim Splitter combination.


9 to 16 Hoses System consists of one Site Controller II, two computer modules, and one C05876

cable and Tokheim Splitter combination.


17 to 24 Hoses System consists of one Site Controller II, three computer modules, and one

C06694 cable and Tokheim Splitter combination.


25 to 32 Hoses System consists of one Site Controller II, four computer modules, and one

C06694 cable and Tokheim Splitter combination.



NOTES:

1.

All Tokheim equipment should be installed per Tokheim specifications.


2.

Wiring trough, conduits, and wire are furnished by the installer.


3. A Model 180 signal cable extension is available as an accessory from Tokheim. The

maximum distance of the combined cables should not exceed 350 feet. The maximum
distance for a 94 or 98 interface box is 250 feet.


4.

Communication for pumps 1-32 may be provided through port 1 or 3 of the Site Controller II.


5.

The second two 98 boxes must be connected to channel 2 of the splitter. Address the third
98 box (first 98 box on channel 2) as pumps 1 to 8; address the fourth 98 box (second 98 box
on channel 2) as pumps 9 to 16.