beautypg.com

Installing the m06184k00x vapor recovery kit, Preparing for the installation, Mounting the emco splitter to dispenser – Gasboy M06184K00X User Manual

Page 6: Caution

background image

Installing the M06184K00X Vapor Recovery Kit

Page 6

MDE-4487C Atlas™ Dispenser Vapor Recovery Kit (M06184K00X) Installation Instructions · September 2008

Installing the M06184K00X Vapor Recovery Kit

Preparing for the Installation

1

Request permission from the Manager/Owner to remove power from the unit and then remove
power using normal procedures. Perform the lockout/tagout safety procedures.

2

Activate the emergency shutoff valve.

3

Ensure that you have the proper kit for the model dispenser to be retrofitted.

4

Be prepared to follow all applicable safety rules and procedures.

Mounting the Emco Splitter to Dispenser

The mounting holes on the dispenser for the Emco Splitter (item

14

) are already on the unit.

Mount the splitter per the following instructions.

Use a UL-approved joint compound on all pipe threads. DO NOT use Teflon

®

tape.

CAUTION

1

Knock out the plastic plugs for the mounting holes near the bottom of the hose side of the
Atlas unit.

2

Using a length of 3/4 inch pipe (nipple) long enough to position the splitter (item

14

) so that

the flange is flush with the dispenser wall, screw the pipe into the splitter. See

Figure 2

.

Figure 2: Mounting 066817 Splitter to Dispenser

1-7/8” - 12 UN per
SAE J475 &
J513 Coaxial
Connection to
Nozzle

3/4” NPT Fuel Connection
from Dispenser

3/4” NPT
Nipple
(not supplied)

Vapor Pipe to
Underground
Tank

Four 5/16-18 x 1”
Screws and Nuts

Dispenser Wall

066817 Splitter
(

Figure 1

on

page 2

)

3/4” Elbow
(not supplied)

Outside of Dispenser

Inside of Dispenser