Installing the m05023k001 kit for suction pumps – Gasboy Q User Manual
Page 6

Installing the M05023K001 Kit for Suction Pumps
Page 6
MDE-4369 Aviation Tubing Retrofit Kit for Gasboy® Q Models Kits M05023K001 & K05023K002 • October 2004
Installing the M05023K001 Kit for Suction Pumps
The following process explains the removal of copper tubing and installation of approved
piping for aviation fuel.
1
Read all instructions before beginning installation.
2
Observe and execute all safety precautions and procedures before, during and after
installation
.
3
Obtain permission from station Operator/Manager to remove pump/dispenser from service
and obtain key to the suction pump door.
4
Turn off all power to the pump and use Tag-Out and Lock-Out procedures.
5
Using the key, open the doors on both sides of the pump.
6
Trip the shear valve and test to ensure that the line is completely closed. (Test by turning
power back on and verify that no fuel can be dispensed. If unit can still function, again retrip
shear valve, making sure that it is completely closed.)
Note: In the next step, before loosing any bolts, reduce the pressure in the lines.
7
Station catch basins and absorbent materials in such a way as to catch any fuel still left in any
open lines (after reducing pressure in the lines).
8
With eye protection in place, remove the copper tubing between the suction pump and meter.
Save all bolts for later use. See
Figure 1: Copper Tubing in Suction Pump Unit
Copper Tubing