Diagnostics Procedure for Cold Weather Problems

Diagnostics Procedure for Cold Weather Problems

Figure 4-1

shows the flow chart of diagnostics procedure for cold weather problems for Atlas

9862 DEF units.

Figure 4-1: Flow Chart

STOP
Below

Operating

Temperature

Specs.

YES

NO

Wait Until Local

Temperature

Increases

and Warms

Test 9800

CPU

Board

PROBLEM 1

Hear Fan ON

Feel Heat in Lower Cabinet

Feel Heaters

YES

Verify

Solenoid

Valve is

Open

NO

NO

Coriolis
Interface
CR1 and
CR2 ON

YES

NO

Replace

Coriolis

Meter

M10006A003

Temperature Control Board

CR1 and CR2 is ON

Replace

Power

Supply

M04151B005

YES

Test Fuse on

Heater/Fan

Assembly

Replace

Heater and

Fan

Assembly if

Fuse is good

NO

YES

NO

YES

YES

YES

YES

NO

NO

NO

NO

NO

Verify

110 VAC

is on P3 AC

Input

Connector

Temperature

Control Board

Mearure for

+5 VDC

at TP1 and TP2

Temperature

Control Board

Mearure

+5 VDC

on P130 Pin 1

Measure

110 VAC

at P1301A at Pins

1 and 4

Replace

Temperature

Control

Board

Replace

Bottom

Temperature

Sensor

Verify

110 VAC

is Measured

at J-box

Check Power

Cable

Connection to

Temperature

Control

Board

Coriolis

Interface

Board

Measure

+5 VDC at

J1401 Pins

1 and 3

Check Circuit

Breaker is ON

9800 CPU Board

Measure +5 VDC at

P9 Pins 1 and 6

No or Low

Voltage

Measured

YES

Is

Outside

Temperature

Below - 30

DISPLAY

999

No Product

Frozen Condition: The coriolis interface board monitors the temperature at the
solenoid valve using the temperature sensor known as the frozen thermostat. The
purpose is to remove power to signal the 9800 CPU board not to active the solenoid
valve on the coriolis meter. This prevents the solenoid valve to potentially leak and
also prevent damage to the coriolis meter.
The CR5 LED on the coriolis interface board will light when a freeze condition
exists, which is normally caused by other component failure, causing the heaters
not to turn on as shown

Figure 4-1

.

Calibration Test: When the freeze problem has been
corrected and the heater/fans are working, to keep the inside
cabinet temperature in 30° F (-1.1° C) range or higher, you
need to recalibrate the unit to remove the error message 999
displayed.

Symptoms: In very cold weather conditions, the display shows 999 and is unable to dispense product.