Conduit, Wiring diagrams, 9100k/8700k series wiring diagram – Gasboy 9216K User Manual
Page 22: Conduit wiring diagrams, Wiring, Diagrams

Wiring
Conduit
Page 18
MDE-4906 Atlas™ 9216K/9216KTW Satellite Dispensers Installation/Operation Manual · June 2010
Conduit
All wiring to the satellite dispensing unit must be installed in threaded, rigid, metal conduit.
PVC is not acceptable.
All wiring and conduit runs must also conform with the NEC (NFPA 70) and the Automotive
and Marine Service Station Code (NFPA 30A). All wiring and conduit runs must conform to
Local codes. Canadian users must also comply with the Canadian Electrical Code.
Wiring Diagrams
The following section contains wiring notes and wiring diagrams for both Atlas mechanical
and electronic pumps. For pump/dispenser model and follow all notes, refer to the appropriate
wiring diagram. For more information, refer to FE-361 Atlas Master and Satellite Field Wiring
Diagram.
Note: Ensure that the correct wiring diagram is used. Incorrect wiring of a 9800K Series unit
will cause damage to the CPU PCB.
Wiring diagrams show simultaneous and non-simultaneous operation of master and satellite
dispensers. Ensure that the correct wiring diagram is used for the suitable application.
9100K/8700K Series Wiring Diagram
Models - Satellite 9216K/9153K, 9153KX, 9152KTW, 9153KTW, 9153KXTW, 9140K,
9140KX, 9216K/8753K, 8753KX, 8752KTW, 8753KTW, 8753KXTW
Notes: 1) All wiring and conduit runs must conform with all building/fire codes, all Federal,
State, and Local codes, NEC, (NFPA 70), NFPA 30, and Automotive and Marine
Service Station Code (NFPA 30A) codes and regulations.
2) To determine which mode of satellite operation is relevant for your application, refer
to Weights and Measures Handbook 44. In many cases, the satellite must be wired so
that, it cannot dispense the product when the master dispenser is dispensing and vice
versa. Use the correct wiring diagram according to your application.
3) This wiring diagram is intended only to show the connections between the satellite
and the dispenser. For applicable warnings and proper connection of all wires, see
wiring diagram for the master dispenser (according to model number). For the
complete wiring information for the dispenser, refer to MDE-4331 Atlas Fuel
Systems Installation Manual.
4) When a submersible pump is used, submersible starter relays are always
recommended for wiring the dispensers. However, the control circuit is capable of
directly driving a submersible pump up to 1 HP at 115/230 VAC. Any pump over
these ratings will require a submersible starter relay.