Fronius Energy Package User Manual
Page 89
87
EN
Load manage-
ment
(1)
Status
(2)
Controlling
- Control via Energy Manager deactivated.
- Control via Energy Manager is based on the power produced.
- Control via Energy Manager is based on surplus power (with feed-in limits). This
option can only be selected if a meter has been connected. Control via Energy
Manger is based on the amount of energy actually fed into the grid.
(3)
Thresholds
- on: For entering an effective power limit as of which output I/O 1 is to be activated.
Example involving Fronius Energy Package without photovoltaics but with a sec-
ond producer within the home
Second producer on home network:
2000 W
Household consumption:
500 W
Target value set at feed-in point:
0 W
Energy fed into Fronius Solar Battery:
1500 W
Power consumed (AC) by inverter:
1500 W
Energy fed into the public grid:
0 W
Example involving Fronius Energy Package plus a second producer within the
home (with AC max. limiting)
PV system connected to Fronius Symo Hybrid:
1000 W
Second producer on home network:
2000 W
Household consumption:
500 W
Target value set at feed-in point:
0 W
Max. AC power consumption limited to:
1000 W
Energy fed into Fronius Solar Battery:
2000 W
Power consumed (AC) by inverter:
1000 W
Energy fed into the public grid:
500 W
(2)
(3)
(4)
(5)