When choosing the switch-on point, the weather conditions and anticipated insolation
should also be taken into account.
Application example
Switch-on point = 2000 W, switch-off point = 1800 W
If the inverter is outputting 2000 W or above, then the floating switch contact on the inverter
is switched on.
If the inverter output falls to below 1800 W, the floating switch contact is switched off.
Possible applications:
Operating a heat pump or an air-conditioning system using as much self-generated power
as possible
Time / Date
Set the time, date and automatic changeover between summer and winter time
Set time
Set the time (hh:mm:ss or hh:mm am/pm – depending on the setting for the time display
format)
Set date
Set the date (dd.mm.yyyy or mm/dd/yyyy - depending on the setting for the date display
format)
Summer/winter time
Activate/deactivate automatic changeover between summer and winter time
IMPORTANT! The time and date must be set accurately in order for the day and year val-
ues and for the day characteristic to be displayed correctly.
Display settings
Language
Set language for display
Setting range
Set time / Set date / Time display format / Date display format /
Summer/winter time
Time display format
For specifying the time display format
Setting range
12hrs / 24hrs
Factory setting
Depends on country setup
Date display format
For specifying the date display format
Setting range
mm/dd/yyyy / dd.mm.yy
Factory setting
Depends on country setup
Setting range
on / off
Factory setting
on
Setting range
Language / Night mode / Contrast / Illumination