Fronius Energy Package User Manual
Page 114
112
*) If the status code is displayed all the time: Notify a Fronius-trained service engineer.
**) If this status code keeps recurring, contact your system engineer.
Status codes –
Class 5
Class 5 status codes do not generally interfere with feeding energy into the grid, but can
cause restrictions. These status codes are displayed until they are acknowledged by
pressing a key (however, the inverter continues to operate normally in the background).
451
Memory error detected
The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid.
*)
452
Communication error between the pro-
cessors
453
Grid voltage and power stage set are in-
compatible
454
Grid frequency and power stage set are
incompatible
456
Anti-islanding function is no longer being
implemented correctly
457
Grid relay is sticking or the neutral con-
ductor ground voltage is too high
The inverter is not feeding
any energy into the grid.
Check the grounding
(the neutral conductor
ground voltage must be
less than 30 V); *)
458
Error when recording measuring signal
The inverter is not feeding
any energy into the grid.
*)
459
Error when recording the measuring sig-
nal for the insulation test
460
Reference voltage source for the digital
signal processor (DSP) is working out of
tolerance
461
DSP data memory error
462
Error during DC feed monitoring routine
463
Reversed AC polarity, AC connector in-
serted incorrectly
474
RCMU sensor faulty
The inverter is not feeding
any energy into the grid.
**)
475
Insulation fault (connection between so-
lar module and ground)
476
Driver supply voltage too low
480,
481
Functional incompatibility (one or more
PC boards in the inverter are not com-
patible with each other, e.g. after a PC
board has been replaced)
The inverter is not feeding
any energy into the grid.
Update inverter firm-
ware; *)
482
Setup interrupted after initial start-up
The inverter is not feeding
any energy into the grid.
Perform AC reset
(switch automatic circuit
breaker off and on
again); update inverter
firmware; *)
484 -
489
CAN transmit buffer is full
The inverter is not feeding
any energy into the grid.
Perform AC reset
(switch automatic circuit
breaker off and on
again); update inverter
firmware; *)
Code
Description
Behaviour
Remedy