beautypg.com

Delta Electronics Modbus TCP Remote I/O Communication Module RTU-EN01 User Manual

Page 5

background image

Modbus TCP Remote I/O Communication Module RTU-EN01

DVP-PLC Operation Manual

3

1 Introduction

To ensure correct installation and operation of RTU-EN01, please read this manual carefully before using your

RTU-EN01. RTU-EN01is an Ethernet remote I/O module for remote setting through Delta’s DCISoft. RTU-EN01

supports maximum 256 digital input/output points. RTU-EN01 supports Modbus TCP protocol and can be used

for remote monitoring with graphic control software or human machine interface. RTU-EN01 can also be used as

a Modbus TCP gateway, supporting the conversion from Modbus TCP commands to Modbus ASCII/RTU. In

addition, in MDI/MDI-X auto-detect, jump wire is not needed when you choose the network cable.

1.1 Features

z

Supporting smart PLC functions, counter, timer and real-time clock. Able to operate independently without

control of PLC main processing unit or programming.

z

Able to auto-detect 10/100 Mbps transmission speed; MDI/MDI-X auto-detect.

z

Supporting maximum 16 digital input/output modules (Max. 256 I/O points) and 8 analog input/output

modules.

z

Supporting maximum 16 sets of Modbus TCP connections.

z

Supporting Modbus TCP/Modbus gateway (supporting Master mode, connectable to maximum 32 devices).

z

Parameters can be set up on webpage.

1.2 Specifications

„

Ethernet

interface

Interface RJ-45

with

Auto

MDI/MDIX

Transmission method

802.3, 802.3u

Transmission cable

Category 5e, 100m (Max)

Transmission speed

10/100 Mbps Auto-Detection

Communication protocol

ICMP, IP, TCP, UDP, DHCP, NTP, Modbus TCP, HTTP

„

Serial communication interface (COM1)

Interface Mini

Dim

Transmission method

RS-232

Communication speed

19,200 bps

Communication format

Stop bit: 1; Parity bit: None; Data bit: 8

Communication protocol

Delta Configuration

Transmission cable

DVPACAB215 / DVPACAB230 / DVPACAB2A30

„

Serial communication interface (COM2)

Interface

3 PIN feed-through terminal

Transmission method

RS-485

Transmission distance

1,200m

Communication speed

110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200

bps

Communication format

Stop bit: 1, 2; Parity bit: None, Odd, Even; Data bit: 7, 8

Communication protocol