Modbus TCP Remote I/O Communication Module RTU-EN01

DVP-PLC Operation Manual

43

7.16 Smart PLC: Timer

Application

Setting up Smart PLC functions by DCISoft. After RY0 is On for 1 second, it will turn Off for 500
ms. This will repeat in cycle.

Steps

(1) Set up the timer: Timer 0 1s, Timer 1 500ms.
(2) Set up IF-THEN: When the timing reaches the target, RY0 will be On or Off.

1. Open the setup page and switch to “Smart PLC” page. Further switch to the “Timer” page.

2. Check to “Enable” Timer 0 and Timer 1 and set Timer 0 to “1s” and Timer 1 to “500ms”. Click “Apply” to

write the settings into RTU-EN01.