Thank you very much for purchasing DELTA DTC1000/2000 Series Temperature Controller. Please read this
instruction sheet before using your DTC1000/2000 series to ensure proper operation, and please keep this instruction
sheet handy for quick reference.

 

Caution

DANGER! Caution! Electric Shock!

DTC1000/2000 series is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne
dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may
occur.

WARNING!

1. Prevent dust or metallic debris from falling into the controller that will cause malfunction. DO NOT modify or

disassemble the controller. DO NO use extra terminals.

2. Do not install and/or use the controller in places subject to:

ƒ

dust or corrosive gases and liquid ƒ high humidity and high radiation ƒ vibration and shock

3. Switch off the power when wiring or changing input sensors.
4. Be sure to use compensating wires that match the thermocouple types when extending or connecting the

thermocouple wires.

5. Shorten the wire when wiring a platinum resistance thermometer (RTD) to the controller, and separate power cable

from load wires to prevent interference and conductive influence.

6. Make sure the power cable and signals device are installed correctly before switching on the power of

DTC1000/2000; otherwise serious damage may occur.

7. DO NOT touch the terminals or repair the controller when the power is on to prevent electric shock.
8. Wait at least one minute after the power is off to allow the capacitor to discharge. DO NOT touch any internal circuit

within this period.

9. DO NOT touch the internal terminals no matter the power is on or off.
10. DO NOT place other heating source (e.g. power supply) in parallel with DTC1000/2000 during the installation.

Please keep proper space in between.

 

Model Name Explanation

D T C 1

2

3

4

5

Series name

DTC: Delta C series temperature controller

1 Controller position

1: First controller
2: Controller connected in parallel

2 Auxiliary output

groups

0: standard, 2 outputs, no auxiliary output
1: 1 auxiliary output. Not available now.
2: 2 auxiliary outputs. Not available now.

3 4 Optional

00: Standard
01: CT input. Not available now.
02: EVENT input. Not available now.

5 Main output type

R: Relay output SPST, 250VAC, 3A
V: Voltage pulse output 12V +10% ~ -20%
C: Current output 4 ~ 20mA
L: Linear voltage output 0 ~ 10V

Enclosed functions: DC24V input, 2 outputs, relay output for output 2, RS-485 communication.

 

Function & Specification

Power supply

DC24V. Isolated switching power

Voltage range

Rated voltage: 90% ~ 110%

Power consumption

Rated 24 VDC, Max. 24 W combined, 3W + 3W x number of DTC2000 controllers (Max. 7)
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Platinum RTD: Pt100, JPt100

Input sensors

Linear DC input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mV

Sampling rate

Analog input: 0.15 sec. Thermocouple or platinum RTD: 0.4 sec.

Control method

PID , programmable PID, Manual, ON/OFF
Relay: SPST, Max. load 250VAC, 3A resistive load
Voltage pulse: 12VDC, Max. output current: 40mA
Current: DC 4 ~ 20mA (Load resistance: < 500Ω)

Output types

Analog voltage: 0 ~ 10V (Load resistance: > 1,000Ω)

Output function

Control output, alarm output, proportional output
Proportional output is available only when output 1 is linear voltage/current output.

Alarm

12 alarm modes

Communication

RS-485 digital communication, 2,400bps ~ 38,400bps

Communication protocol Modbus protocol, ASCII/RTU format
Internal connection

Internal terminals available to transmit 24V power supply and communication signals

Vibration resistance

10 ~ 55Hz, 10m/s

2

for 10mins, each in X, Y and Z direction

Shock resistance

Max. 300m/s

2

, 3 times in each 3 axes, 6 directions

Ambient temperature

0 ~ 50

°

C

Storage temperature

-20 ~

+65

°

C

Altitude <

2,000m

Ambient humidity

35% ~ 85% RH (non-condensing)

Pollution degree

2

 

Product Profile & Outline

DTC1000R/V/C/L

1 RUN/STOP

switch

2

Wiring and Model name

3

DIN rail clip

4 I/O

terminals

5 LED

indicators

6 Mounting

hole

7 Specification

label

8 Extension

port

9 Extension

clip

10 DIN rail
11 RS-485 communication port
12 Extension clip
13 DC power input

9

0

.0

3

.0

60.0

3.4

25.2

4

.0

3

.0

1

2

3

4
5

6

7

8

9

10

3

11

12

13

DTC2000R/V/C/L

1

Wiring and Model name

2

DIN rail clip

3 I/O

terminals

4 LED

indicators

5 Mounting

hole

6 Specification

label

7 Extension

port

8 Extension

clip

9 DIN

rail

9

0

.0

3

.0

60.0

3.4

25.2

4

.0

3

.0

1

2

3
4

5

6

7

8

9

2

10

10 Extension port

 

Input

DTC1000/2000 series supports the following input sensors:

Input Sensor

Register Value

Available Range

0 ~ 50mV linear voltage input

17

0 ~ 50mV

4 ~ 20mA linear current input

16

4 ~ 20mA

0 ~ 20mA linear current input

15

0 ~ 20mA

0 ~ 10V linear voltage input

14

0 ~ 10V

0 ~ 5V linear voltage input

13

0 ~ 5V

Platinum RTD (Pt100)

12

-200 ~ 600

°

C (-328 ~ 1,112

°

F)

Platinum RTD (JPt100)

11

-20 ~ 400

°

C (-4 ~ 752

°

F)

Thermocouple TXK type

10

-200 ~ 800

°

C (-328 ~ 1,472

°

F)

Thermocouple U type

9

-200 ~ 500

°

C (-328 ~ 932

°

F)

Thermocouple L type

8

-200 ~ 850

o

C (-328 ~ 1562

°

F)

Thermocouple B type

7

100 ~ 1,800

°

C (212 ~ 3,272

°

F)

Thermocouple S type

6

0 ~ 1,700

°

C (32 ~ 3,092

°

F)

Thermocouple R type

5

0 ~ 1,700

°

C (32 ~ 3,092

°

F)

Thermocouple N type

4

-200 ~ 1,300

°

C (-328 ~ 2,372

°

F)

Thermocouple E type

3

0 ~ 600

°

C (32 ~1,112

°

F)

Thermocouple T type

2

-200 ~ 400

°

C (-328 ~ 752

°

F)

Thermocouple J type

1

-100 ~ 1,200

°

C (-148 ~ 2,192

°

F)

Thermocouple K type

0

-200 ~ 1,300

°

C (-328 ~ 2,372

°

F)

Note 1: The current input is built-in with 249Ω precision resistor. See “How To Set up Current Input” section.
Note 2: Default setting: Pt100 input.

The range of linear input and feedback value is adjustable. Range of input feedback: -999 ~ 9,999. Take 0 ~ 20mA input
as example, -999 refers to 0mA input, and 9,999 refers to 20mA input. If we change the range to 0 ~ 2,000, 0 will refer to
0mA input, and 2,000 will refer to 20mA input. 1 display scale = 0.01mA.

 

Output

There are several output types available from DTC1000/2000 series: Control Output (heating/cooling), Alarm Output
and Proportional Output.

y

Control Output

DTC1000/2000 series offers 2 outputs for heating or cooling control. If you require dual loop output, the 2 outputs
should be set to different actions (heating or cooling). If you require the 2 outputs are set to the same control action, only
the control cycle of output 1 will be valid, and the 2 outputs will act at the same time.

The control methods include: PID control, ON/OFF control, Manual control and programmable PID control.

y

Single Output Control

Heating hysteresis

ON

OFF

PV

Figure1: ON/OFF Control

Cooling hysteresis

Heating

Cooling

Set Point

Set Point

PV

100%

0

Heating

Output

PV

100%

0

Output

Set Point

Cooling

Set Point

Figure 2: PID Control, Cooling) Control

Figure 3: PID Control, Heating Control


y

Dual Output Control

OFF

PV

Set Point

ON

Heating

Deadband

Heating hysteresis

Figure 4:

ON/OFF Control

Cooling hysteresis

Cooling

Deadband: Dead
Bandwidth: Negative

PV

0

PV

0

Deadband: Dead
Bandwidth: Positive

Output

Heating

Cooling

Set Point

Output

Heating

Cooling

Set Point

Figure 5: PID control

Figure 6: PID Control

y

Programmable PID Control & Parameters Setting

The programmable PID control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0 ~ 7) and
parameters: “link pattern”, “cycle” and “the number of steps”.

Start Pattern:
The user can set up which pattern is the start pattern for the programmable control.

Steps:
Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV)
has to rise to temperature X after the period of execution time T. If the result of the set point X is the same as that of
the previous setting, the process is called “Soak”; otherwise, it is called “Ramp”. Therefore, the programmable control
is also known as Ramp/Soak control. The default setting of the first step is Soak control. The temperature will first rise
to the set point X and remain at X. The total execution time is T.

Link Pattern: The pattern to be executed following the current pattern. If the setting is not 0 ~ 7, the set point will
remain at the last pattern.

Cycle:
The additional number of cycles for a pattern. For example, if the parameter is set to 2, it refers to the pattern
has to execute additional twice, totaling the execution to 3 times including the original one.

The Number of Steps:
The number of steps in each pattern (range: 0 ~ 7). For example, if the parameter is set to 2,
it refers to the pattern will execute Step 0 ~ Step 2, and other steps will not be executed.

The Execution: Available settings include “run”, “program hold”, “program stop” or “stop”.
1. When this parameter is set to “run”, the program will start its execution from step 0 of the start pattern.
2. When this parameter is set to “program hold”, the program will stop and the temperature will stop at the SV before

the program stops. If the user sets to “run” again, the program will resume the step before the program stops and
execute by the remaining time.

3. When this parameter is set to “program stop”, the program will stop and the temperature will stop at the SV before

the program stops. If the user sets to “run” again, the program will execute again from Step 0 of the start pattern.

4. When this parameter is set to “stop”, the program will stop, and the control output will be disabled.

Proportional Output:
If Output 1 of this DTC1000/2000 series is linear voltage or current, the user can set it to “Proportional Output”.
Proportional output refers to the output varies with the input. For example, if the input range is set to 0 ~ 1,000, and
when the input value is 0, the output will be 0mA or 0V. When the input value is 1,000, the output will be 20mA or 10V.

Figure 7: Proportional Output

Output

PV Low

PV High

Output

10V or 20mA

0V or 4mA

PV Low

PV High

Negative
output slope

PV

PV

Positive output slope

10V or 20mA

0V or 4mA

y

Alarm Output

DTC1000/2000 series offers 12 alarm modes. When the PV exceeds or falls below SV, the alarm output will be enabled.
See the table below for the 12 modes.

Mode

Alarm Type

Alarm Output Operation

0 No

alarm

OFF

1

Alarm output will be enabled when the temperature reaches upper and lower
limits.
y

Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV –

AL-L.

ON

OFF

AL-L

SV

AL-H