Warning

This instruction sheet provides only information on the electrical specification, general functions, installation and
wiring. The program design and applicable instructions for DVP-EC3 are the same as those applicable for DVP-ES
series. For detailed information, please refer to “DVP-PLC Application Manual: Programming”. For details of the
optional peripheral, please refer to the instruction sheet enclosed in it.

DVP-EC3 series PLC is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne
dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device
may occur.

DO NOT connect the input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check
all the wiring again before switching on the power. Make sure the ground terminal

is correctly grounded in order

to prevent electromagnetic interference.

Introduction

Thank you for choosing Delta DVP-EC3 series programmable logic controller. DVP-EC3 currently offers 10-16
I/O points. To ensure proper installation, operation and maintenance, please read this instruction sheet carefully
and provide users with this instruction sheet before installing DVP-EC3.

Product Profile & Outline

+24 V24 G S/ S X 0 X 1 X 2 X3 X 4 X5 X 6 X 7

L

N

C 0 Y0 Y1 Y 2 Y 3 C 1 Y 4 Y 5

POWE R

R UN

ER ROR

DVP1 6EC

8DI-DC / 8DO-R

D ir ec t m oun ting ho l e

Inpu t po ints Ind i c atio n

D C p ow e r s u pp l y o u tpu t

I/O p oin t in di ca to rs

C OM 1 C om mu n i ca tion

(RS-23 2C)

por t

D IN r ai l (35m m)

D ir ec t m ou ntin g ho l e

F ix ed I/O te r min als

D IN rai l c li p

P OW ER , R U N & ER RO R i n dic a tors

O utp ut poi nts In d ic a tio n

A C p ow e r s u pp l y in put

C OM 2 C om mun i ca ti on

(RS- 48 5 )

p ort

D + D - S G

Y 6 Y 7

M od el n a me

COM2

COM1

Dimensions

9 0.5 m m

95 m m

4 8.5 m m

90m m

99 m m

+24V 24G S/S X0 X1

X2 X3

X4 X5 X6 X7

IN

OUT

PO WE R

R U N

E R RO R

L

N

C0

Y0 Y1 Y2

Y3 C1 Y4

Y5

DVP16EC

8DI-DC / 8DO-R

I NP U T

A C 1 00 ~2 4 0V

0 1 2 3 4 5 6 7

0 1 2 3 4 5 6 7

D+ D- SG

Y6 Y7

C OM2

C OM1

ENGLISH

Specifications

Model

Item

DVP10EC00

□3

DVP14EC00

□3

DVP16EC00

□3

Power supply voltage

100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5%

Operation

DVP-EC3 starts to run when the power supply rises to 95 ~ 100V AC and stops
when the power supply drops to 70V AC. It continues to run for 10ms after the
power supply is cut off.

Power supply fuse

2A/250V AC

Power consumption

9VA

DC24V Supply Current

100mA

Power supply protection

DC24V output short circuit protection

Voltage withstand

1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC
(Secondary-PE)

Insulation resistance

> 5MΩ at 500V DC (between all I/O points and earth)

Noise immunity

ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
RS: 26MHz ~ 1GHz, 10V/m

Earth

The diameter of grounding wire shall not be less than that of L, N terminal of the
power supply. (When many PLCs are in use at the same time, please make sure
every PLC is properly grounded.)

Operation/storage

Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)

Vibration/shock
resistance

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC
68-2-27 (TEST Ea)

RS-485 communication
mode

Not supported

Not supported

Supported

Weight (g)

R: 192g; T: 180g

R: 202g; T: 185g

R: 212g; T: 190g

Input Point

Input point type

Digital Input

Input type

DC (SINK or SOURCE)

Input current

24V DC 5mA

Off → On, > 15V DC

Action level

On → Off, < 5V DC

Reaction time
(Conversion sampling
time)

Approx. 10ms (0 ~ 20ms adjustable in D1020)

Output Point

Output point type

Relay-R

Transistor-T

Current specification

2A/1 point (5A/COM)

0.5A/1 point (2A/COM)

Voltage specification

< 250V AC, 30V DC

5 ~ 30V DC

(UP, ZP must work wit external

auxiliary power supply 24V DC -15%

~ +20%, rated consumption approx.

1mA/point)

75VA (inductive)

Maximum load

90W (resistive)

15W/1 point (Resistive)

Reaction time

Approx .10ms

Off

→ On 30us, On → Off 100us

Installation & Wiring

3.1 I/O Terminal Layout

◎ DVP10EC00R3/T3

X4

X3

X2

X1

X0

S/S

24G

+24V

X5

Y3

Y2

Y1

Y0

C0

D VP 10EC 00R3 (6DI -DC / 4D O- R)

X4

X3

X2

X1

X0

S/S

24G

+24V

X5

Y3

Y2

Y1

Y0

ZP

UP

DVP10EC00 T3 (6DI- DC / 4DO- T)

◎ DVP14EC00R3/T3

X4

X3

X2

X1

X0

S/S

24G

+24V

X7

X6

X5

Y4

C1

Y3

Y2

Y1

Y0

C0

Y5

DVP14EC00R3 (8DI- DC / 6DO-R)

X4

X3

X2

X1

X0

S/S

24G

+24V

X7

X6

X5

Y4

Y3

Y2

Y1

Y0

ZP

UP

Y5

D VP14EC 00T3 (8DI- DC / 6DO-T)

◎ DVP16EC00R3/T3

X4

X3

X2

X1

X0

S/S

24G

+24V

X7

X6

X5

Y4

C1

Y3

Y2

Y1

Y0

C0

Y5

DVP16EC00R3 (8DI-DC / 8DO-R)

Y6

Y7

SG

D-

D+

X4

X3

X2

X1

X0

S/S

24G

+24V

X7

X6

X5

Y4

Y3

Y2

Y1

Y0

ZP

UP

Y5

DVP16EC00T3 (8DI-DC / 8DO- R)

Y6

Y7

SG

D-

D+

1. Use the 12-24 AWG single-core bare wire or the multi-core wire for the I/O wiring, and please use 60/75°C

copper conductor only. The twisting power of the screw for the DVP-EC3 terminal is 3.80 kg-cm (3.30
lb-in) .

2. DO NOT wire empty terminal. DO NOT place the input signal wire and output power wire in the same

wiring circuit.

3. DO NOT drop tiny metallic conductor into DVP-EC3 while screwing and wiring

3.2 Mounting & Installation

Please install PLC in an enclosure with sufficient space around it to allow heat dissipation. For heat
dissipation, make sure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet.
(See the figure.)

How to screw: Please use M4 screw according to the dimension of the product.

How to install DIN rail: PLC can be secured to a cabinet by using the 35mm DIN rail. When mounting PLC to
DIN rail, be sure to use the end bracket to stop any side-to-side movement of it and reduce the change of
wires being loosen. A small retaining clip is at the bottom of it. To secure PLC to DIN rail, place the clip onto
the rail and gently push it up. To remove it, pull the retaining clip down and gently remove it from DIN rail.

3.3 Wiring Notes

Specification & Wiring of Power Supply

The power supply input for DVP-EC3 model is AC input. When operating DVP-EC3, please make sure that:

1. The input voltage should be 100 ~ 240VAC. The power supply should be connected to L and N terminals.

Please note that wiring AC110V or AC220V to +24V output terminal or digital input points will result in
serious damage on it.

2. Use 1.6mm wire (or longer) for the grounding of it.

3. The power shutdown of less than 10ms will not affect the operation of it. However, power shutdown time

that is too long or the drop of power supply voltage will stop the running of it, and all outputs will go “OFF”.
When the power supply turns normal again, DVP-EC3 will automatically return to its operation. (Please be
aware of the latched auxiliary relays and registers inside DVP-EC3 when programming.)

4. For max. output of the +24V power supply output terminal for each model, please refer to the electrical

specification table. DO NOT connect other external power supplies to this terminal. Every input point
requires 5 ~ 7mA to drive (e.g. 16 input points will require 80 ~ 112mA to drive). The +24V input on DVP-
EC3 is only for digital input points; other external loads are not suggested.

L

100~240VAC

N

24G S/S

X0

X1

X2

2. 0A

DC/DC

5V

+2 4V

Safety Wiring

Since DVP-EC3 controls many devices, actions of any device may affect actions of other devices, and the
breakdown of any one device may cause the breakdown of the entire auto-control system and danger.
Therefore, we suggest you wire a protection circuit at the power supply input terminal, as shown in the figure
below.

1

AC power supply load

2

Power supply circuit protection fuse (3A)

3

POWER indicator

4

Emergency stop: This button can cut off the system
power supply when accidental emergency takes place

5

Breaker

6

DVP-EC3 (main processing unit)

7

Earth resistance: < 100Ω

8

Power supply: 100 ~ 240V AC, 50/60Hz

I/O Point Wiring

The input signal of the input point is the DC power DC input. There are two types of DC type wiring: SINK and
SOURCE, defined as follows:

◎ Input Point Loop Equivalent Circuit & Wiring

DC Signal IN

(SINK mode)

+24 V

24 G

S/ S

X0

+5 V

24V D C

X1

DC Signal IN

(

SOURCE mode)

+24V

24G

S/S

X0

+5V

24VDC

X1

Below is an example. For detailed point configuration, please refer to specifications of each model:

◎ Relay (R) Output Circuit Wiring

1

Flywheel diode: To extend the life span of contact

2

Emergency stop: Uses external switch

3

Fuse: Uses 5 ~ 10A fuse at the shared terminal of
output contacts to protect the output circuit

4

Varistor: To reduce the interference on AC load

5

Empty terminal: Not in use

6

DC power supply

7

Neon indicator

8

AC power supply

9

Incandescent light (resistive load)

10

Manually exclusive output: Uses external circuit and
forms an interlock, together with DVP-EC3 internal
program, to ensure safety protection in case of any
unexpected errors.

◎ Transistor (T) Output Circuit Wiring

1

DC power supply

2

Emergency stop

3

Circuit protection fuse

4

The output of the transistor model is “open
collector”. If Y0/Y1 is set to pulse output, the output
current has to be 0.05 ~ 0.5A to ensure normal
operation of the model.

5

Manually exclusive output: Uses external circuit and
forms an interlock, together with DVP-EC3 internal
program, to ensure safety protection in case of any
unexpected errors.

注意事項

本使用說明書提供給使用者電氣規格、功能規格、安裝配線之相關注意事項。其他詳細之程式設計及指令與
DVP-ES

系列相容,詳細說明請見 DVP-PLC 應用技術手冊【程式篇】,選購之周邊裝置詳細說明請見該產品

隨機使用說明書。

本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊∕衝
擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意
外衝擊本體,造成危險及損壞。

交流輸入電源不可連接於輸入∕出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子 務必正確的接地,可提高產品抗雜訊能力。

產品簡介

感謝您採用台達 DVP-EC3 系列可程式控制器。DVP-EC3 系列目前提供 10 ~ 16 點數的主機。為了確保能夠正確
地安裝及操作可程式邏輯控制器,請在裝機之前,詳細閱讀本使用手冊,並請妥善保存及交由該機器的使用者。

產品外觀及各部介紹

直接 固定孔

固定 式輸 出 / 端 子

C O M 1

程 式通訊口

輸 入 / 出 點指示燈

直接固定 孔

電源、運行及錯 誤指 示燈

直流電源 輸出

輸出點指 標

交流電源 輸入

輸入 點指 標

+24V 24G S/ S X0 X1 X2 X3 X4 X5 X6 X7

L

N

C0 Y0 Y1 Y2 Y3 C1 Y4 Y5

POWE R

RUN

ERROR

D VP1 6EC

8DI-DC / 8DO-R

D IN

( 3 5 mm )

軌槽

( RS - 2 32 C )

D IN

軌固 定扣

C O M 2

通 訊口(RS-48 5)

D+ D- SG

Y6 Y7

機種 型號

C O M1

C O M2

尺寸規格

9 0.5 m m

95 m m

4 8.5 m m

90m m

99 m m

+24V 24G S/S X0

X1

X2 X3

X4

X5 X6 X7

IN

OUT

PO WE R

R U N

E R RO R

L

N

C0

Y0 Y1 Y2 Y3 C1 Y4

Y5

DVP16EC

8DI-DC / 8DO-R

I NP U T

A C 1 00 ~2 4 0V

0 1 2 3 4 5 6 7

0 1 2 3 4 5 6 7

D+ D- SG

Y6

Y7

C OM2

C OM1

繁體中文

電氣規格

機種

項目

DVP10EC00

□3

DVP14EC00

□3

DVP16EC00

□3

電源電壓

100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5%

動作規格

當電源緩升至 95 ~ 100V AC 時,DVP-EC3 開始動作,當電源緩降至 70V AC 時,DVP-EC3

會停止動作。電源瞬間斷電 10ms 以內繼續運行。

電源保險絲容量

2A/250V AC

消耗電力

9VA

DC24V

供應電流 100mA

電源保護

DC24V

輸出具短路保護

突波電壓耐受量

1,500V AC (Primary-secondary)
1,500V AC (Primary-PE)
500V AC (Secondary-PE)

絕緣阻抗

5MΩ

以上(所有輸出/入點對地之間 500V DC)

雜訊免疫力

ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
RS: 26MHz ~ 1GHz, 10V/m

接地

接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地)

操作/儲存環境

操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度)污染等級 2
儲存:-25°C ~ 70°C (溫度),5 ~ 95%(濕度)

耐振動/衝擊

國際標準規範 IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

RS-485

通訊模式

不支援

不支援

支援

重量(約,g)

R

:192g;T:180g

R

:202g;T:185g

R

:212g;T:190g

輸 入 點 電 氣 規 格

輸入點類型

數位輸入

輸入形式

直流(SINK 或 SOURCE)

輸入電流

24VDC

,5mA

Off → On

,15V DC 以上

動作位準

On → Off

,5V DC 以下

反應時間
(轉換取樣時間)

約 10ms(由 D1020 及可作 0 ~ 20ms 的調整)

輸 出 點 電 氣 規 格

輸出點形式

繼電器-R

電晶體-T

電流規格

2A/1

點(5A/COM)

0.5A/1

點(2A/COM)

電壓規格

250V AC, 30V DC

以下

5~30VDC

(UP, ZP

必須外加輔助電源 24V DC -15% ~ +20%

額定消耗約 1mA/點)

75VA

(電感性)

最大負載

90W

(電阻性)

15W/1

點(電阻性)

反應時間

約 10ms

Off → On 30us

,On → Off 100us