Series Valve Temperature Controller

Instruction Sheet


Thanks you very much for choosing Delta DTV series valve temperature controller. Please read this instruction sheet
before using your DTV to ensure proper operation. Keep this instruction handy for quick reference.

 

Warning

DANGER! CAUTION! ELECTRIC SHOCK! When the power is on, DO NOT touch the AC terminals in case an
electric shock may occur. Make sure the power is disconnected when you check the input power.

DTV is an OPEN-TYPE device. If it will cause serious injury to workers or damage on other equipments when
used in a dangerous environment, please make sure it is installed in an automatic safety protection device.

1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, Max. width 7.2mm). Please be sure

to tighten them properly and make sure the wire is connected to the correct terminal.

2. Prevent dust or metallic debris from falling into the device and cause malfunction. DO NOT modify or uninstall DTV series

without being permitted. DO NOT use empty terminals.

3. Keep away from high-voltage and high-frequency environment during installation in case of interference. Prevent using DTV

in premises which contain:

(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration

4. The power has to be switched off when wiring or changing temperature sensor.
5. Make sure to use compensation wire which matches the thermocouple when extending or connecting the thermocouple wire.
6. Use wires with resistance when extending or connecting the platinum resistance sensor.
7. Keep the wire as short as possible when wiring a sensor to the temperature controller. Separate the power cable and load

wire in order to prevent interference and induced noise.

8. DTV is an open-type device. Make sure to install it in an enclosure which prevents dust and humidity in case of an electric

shock.

9. Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious

damage may occur.

10. DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur.
11. Please wait for one minute after the power is switched off to allow the capacitor to discharge. DO NOT touch the internal

wiring within this period.

12. DO use dry cloth and DONOT use acid or alkaline liquid to clean the device.

 

Display, LED & Pushbuttons

PV: Present value
SV: Set value
%: Output percentage
AT: Auto-tuning indicator
A/M: Manual control indicator
OUT1/OUT2: Output indicator
ALM1/ALM2: Alarm output indicator

Manual/auto mode switch key

Selection/setup key

Switching page key

Left-shifting the digit

Adjusting numbers

 

Ordering information

DTV

1 2 3 4 5

Series name

DTV: Delta V series valve temperature
controller

1 2 3 4

Panel size
(W × H)

4896: 1/8 DIN W48 × H96 mm
9696: 1/4 DIN W96 × H96 mm

5

R: Valve, relay output SPST (250VAC, 5A)

 

Specifications

Power input

AC100 ~ 240V, 50/60Hz

Input power range

85% ~ 110%, rated voltage

Power consumption

Less than 5VA

Display

2-line, 7-segment LED, 4bits and 2 bits of valve openness display
PV in red, SV and valve openness in green.
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Platinum resistance: Pt100, JPt100

Input temperature
sensor

Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mA

Control method

PID, PID programmable control, manual, On/Off

Control output type

Relay output: SPST, Max. load 250V, 5A resistive load

Display scale

1 digit after the decimal point, or no decimal point

Sampling cycle

Analog input: 0.15 sec; thermocouple/platinum resistance: 0.4 sec

Vibration resistance

10 ~ 55Hz 10m/s

2

3 axes 10 min.

Shock resistance

Max. 300m/s

2

3 axes 6 directions, 3 times each

Ambient temperature

0°C ~ +50°C

Storage temperature

-20°C ~ +65°C

Operation altitude

Less than 2,000m

Ambient humidity

35% to 80% RH (non-condensing)

 

Setting up Parameters

Switching Modes: DTV is in the operation mode when the power is switched on, displaying PV and SV. Press

for

more than 3 seconds to enter the initial setting mode. Press

for less than 3 seconds in the operation mode to enter

the regulation mode. Press

once in the regulation or initial setting mode to return to the operation mode.

Selecting parameters: In the operation, regulation or initial setting mode, press

to select parameters for setup.

Setting up number parameters: Find the parameters to be set up or modified. Use

to modify the settings.

Press

to move to the desired digit to be modified and the digit will flash. Press

to complete and save the

setting.
Setting up non-number parameters: Find the parameter to be set up or modified and use

to modify the

setting. The parameter will flash at this time. Press

to complete and save the setting.

Regulation

Mode

Operation

Mode

Initial Setting

Mode

Press for less than 3 secs

Press for more than 3 secs

Press

Press

Regulation Mode

Operation Mode

Initial Setting Mode

Auto-tuning

(Set up when in PID control and RUN)
Press

V

Use

to set up SV


Press

V

Set up input type


Press

V

Select the PID group (0 ~ 4)

(4 groups of PID are available in PID
control. n = 4: PID is auto-selected.
See the next table.)
Press

V

Control loop RUN/STOP




Press

V

Set up temperature unit

(Not displayed when in analog input
mode)

Press

V

PD control offset



Press

V

Start setting up patterns

(Set up when in PID programmable
control mode)
Press

V

Upper limit for the temperature

range

Press

V

Heating hysteresis setting

(Set up when in On/Off control)

Press

V

Set up the position of decimal

point
(Not for thermocouple B, R, S type)
Press

V

Lower limit for the temperature

range

Press

V

Cooling hysteresis setting

(Set up when in On/Off control)


Press

V

Upper limit for alarm 1

(Adjustable when ALA1 is enabled)


Press

V

Select control mode

(Enter step editing when PID
programmable control is selected.
See the next table)
Press

V

/

Heating/cooling control

cycle
Press

V

Lower limit for alarm 1

(Adjustable when ALA1 is enabled)
Press

V

Select heating or cooling


Press

V

Switch for valve feedback

setting

Press

V

Upper limit for alarm 2

(Adjustable when ALA2 is enabled)
Press

V

Set up alarm mode 1


Press

V

Auto adjusting feedback value

(Displayed when in valve feedback
mode and STOP)
Press

V

Lower limit for alarm 2

(Adjustable when ALA2 is enabled)

Press

V

Set up alarm mode 2



Press

V

Time from valve fully closed to

fully open
Press

V

Key-locked mode


Press

V

Set up system alarm


Press

V

Valve DeadBand Setting




Press

V

Displaying and adjusting

output percentage
(Displayed when in PID mode and
manual RUN)
Press

V

Enable/disable communication

write-in


Press

V

Upper limit adjusting with

feedback output
(Displayed when in valve feedback
mode)
Press

V

Output percentage of valve

feedback
(Displayed when there is valve
feedback)
Press

V

Select ASCII/RTU

communication format


Press

V

Lower limit adjusting with

feedback output
(Displayed when in valve feedback
mode)
Press

V

D/A value of valve feedback

(Displayed when there is valve
feedback)

Press

Z

Back to top

Set up communication

address


Press

V

Adjusting PV offset

Press

V

Set up baud rate

Press

V

Upper limit for control output

Press

V

Set up data length

Press

V

Lower limit for control output

Press

Z

Back to top

Set up stop bit

Press

Z

Back to top

Select the PID group: The user can select one of the 4 groups. When n = 4, the program will automatically select the
PID group that is the closest to the SV.

Select the PID group (n = 0~4)

Press

Z

PID group 0 ~ 3

Set up the temperature SV for

PID group 0
Press

V

Set up the temperature SV for

PID group 3
Press

V

Set up the proportion band for

PID group 0
Press

V

Set up the proportion band for

PID group 3
Press

V

Set up the Ti value for PID

group 0
Press

V

Set up the Ti value for PID

group 3
Press

V

Set up the Td value for PID

group 0
Press

V

Set up the Td value for PID

group 3
Press

V

Set up the integration offset

for PID group 0, AT auto-setting
Pres

Z

PD control offset

Set up the integration offset

for PID group 3, AT auto-setting
Press

Z

PD control offset

Editing patterns and steps: In parameter

, select

for editing. Take pattern 0 for example:

Select the pattern No. to be

edited

Select No.

Z

Press

V

Select OFF

Edit the temperature in step 0



Press

V

Select the actual number of

steps in the program

Press

V

Leave pattern and step editing

V

Edit the time for step 0

(unit: hour/minute)

Set up the number of

additional cycles (0 ~ 99)

Continue the setup in

Press

V

Press

V

Set up from step 0 ~ step 7 in order

Set up the link pattern.

OFF = end of program
Press

V

Edit the temperature in step 7

Press

V

Return to “select the pattern No. to be
edited”

Edit the time for step 7

(unit: hour/minute)
Press

V

Following the actual number of steps

 

Output Control

DTV offers heating and cooling outputs.

In parameter

, you can select either to operate heating control or cooling control. Select

for heating

output and

for cooling output.

PV

OFF

ON

Heating hysteresis

Cooling hysteresis

Heating

Cooling

Set point

Figure 1: Output operation when in On/Off control

PV

Output

Heating

Cooling

Set point

Figure 2: PID control

Key-locked Function

: Lock all the keys on the panel.
: Only SV can be modified.
: Only SV and auto/manual mode can be modified (The control mode has to be PID control).

Press

and

at the same time to unlock the keys.

 

Types of Temperature Sensors & Temperature Range

Input Sensor Type

Register Value

Display

Range

0 ~ 50mV analog input

17

-999 ~ 9,999

4 ~ 20mA analog input

16

-999 ~ 9,999

0 ~ 20mA analog input

15

-999 ~ 9,999

0V ~ 10V analog input

14

-999 ~ 9,999

0V ~ 5V analog input

13

-999 ~ 9,999

Platinum resistance (Pt100)

12

-200 ~ 600°C

Platinum resistance (JPt100)

11

-20 ~ 400°C

Thermocouple TXK type

10

-200 ~ 800°C

Thermocouple U type

9

-200 ~ 500°C

Thermocouple L type

8

-200 ~ 850°C

Thermocouple B type

7

100 ~ 1,800°C

Thermocouple S type

6

0 ~ 1,700°C

Thermocouple R type

5

0 ~ 1,700°C

Thermocouple N type

4

-200 ~ 1,300°C

Thermocouple E type

3

0 ~ 600°C

Thermocouple T type

2

-200 ~ 400°C

Thermocouple J type

1

-100 ~ 1,200°C

Thermocouple K type

0

-200 ~ 1,300°C

Note 1: The current input is built-in with a 249Ω precision resistor. See “How to Set up Current Input” section.
Note 2: The default setting is Pt100 input.

Note 3: To display the decimal point, you have to set up the parameter

(in the operation mode). The decimal point display is available for all

modes except for thermocouple B, R, and S type.

Note 4: The range for analog input is -999 ~ 9,999. Take 0 ~ 20mA for example, -999 refers to 0mA input and 9,999 refers to 20mA input. If we change

the range into 0 ~ 2,000, 0 will thus refer to 0mA input and 2,000 refers to 20mA input (1 display scale = 0.01mA).

 

Alarm Output

DTV offers 2 groups of alarm outputs and 17 modes for each group under the initial setting mode. When the PV
exceeds or falls below SV, the alarm output will be enabled. See the table below for the 17 alarm output modes.

Mode

Alarm Type

Alarm Output Operation

0

No alarm

Off

1

Alarm output is enabled when the temperature reaches upper and lower limits.
Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV - AL-L.

ON

OFF

AL-L

SV

AL-H

2

Alarm output will be enabled when the temperature reaches the upper limit.
Alarm will be enabled when the PV exceeds SV + AL-H.

ON

OFF

SV

AL-H

3

Alarm output is enabled when the temperature reaches the lower limit.
Alarm will be enabled when the PV falls below SV – AL-L.

ON

OFF

AL-L

SV

4

Alarm output will be enabled when the PV is between SV + AL-H and SV – AL-L.

ON

OFF

AL-L

SV

AL-H

5

Alarm output is enabled when the temperature reaches the absolute value of the upper
and lower limits.
Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.

ON

OFF

AL-L

AL-H

6

Alarm output is enabled when the temperature reaches the absolute value of the upper
limit.
Alarm will be enabled when the PV exceeds AL-H.

ON

OFF

AL-H

7

Alarm output is enabled when the temperature reaches the absolute value of the lower
limit.
Alarm will be enabled when the PV falls below AL-L.

ON

OFF

AL-L