Modbus TCP Remote I/O Communication Module RTU-EN01
DVP-PLC Operation Manual
12
B R # 5 0 ~ B R # 5 7 : R T C S e t t i n g s
Explanations:
For setting up the real-time clock (RTC). When BR#9 = 1, RTU-EN01 will stop to update the RTC values to
BR#10 ~ #16. Once the setup is completed, RTU-EN01 will set BR#9 to 0.
Allowed range for RTC: 1970/01/01 00:00:00 ~ 2037/12/31 23:59:59
BR#9
0 No
action
1 RTC
stops
2
RTC being set
4.3 External Input Contacts (RX)
RX#
Attribute
Content
Explanation
Default
Latched
0 ~ 255
R/W
External input contact
Input points on analog I/O module
OFF
NO
Symbol “R” refers to ready only; “R/W” refers to read and write.
R X # 0 ~ # 2 5 5 : E x t e r n a l I n p u t C o n ta c t
Explanations:
The right-side extension interface on RTU-EN01 is able to connect to DVP-Slim series digital I/O modules.
RTU-EN01 supports maximum 256 I/O points.
4.4 External Output Contacts (RY)
RY#
Attribute
Content
Explanation
Default
Latched
0 ~ 255
R/W
External output contact Output points on analog I/O module
OFF
NO
Symbol “R” refers to ready only; “R/W” refers to read and write.
RY # 0 ~ # 2 5 5 : E x t e r n a l O u t p u t C o n ta c t
Explanations:
The right-side extension interface on RTU-EN01 is able to connect to DVP-Slim series digital I/O modules.
RTU-EN01 supports maximum 256 I/O points.
4.5 Control Register for Extension Modules (RCR)
RCR#
Attribute
Content
Explanation
Default
Latched
0 ~ 49
R/W
The 1
st
analog I/O
module
Control register for the 1
st
analog I/O
module
-- NO
50 ~ 99
R/W
The 2
nd
analog I/O
module
Control register for the 2
nd
analog I/O
module
-- NO
100 ~ 149
R/W
The 3
rd
analog I/O
module
Control register for the 3
rd
analog I/O
module
-- NO
150 ~ 199
R/W
The 4
th
analog I/O
module
Control register for the 4
th
analog I/O
module
-- NO