Delta Electronics SSW 230 V - 20 kVA User Manual
The static switch product line, Description, Features
SSW 230V-6kVA →
SSW 230 V – 20 kVA →
Description:
The static switch product line is a micro-controller driven
state-of-the-art switch between the AC mains and the
inverter to provide uninterruptible AC power. After an
extremely quick detection of a mains fault, the static
switch transfers the load almost without cut off to the
redundant AC line. A communication and synchronization
bus is responsible for the system performance and the
Delta inverters are synchronized to the public AC mains.
Modular UPS configurations in ON LINE or OFF LINE
mode can be realized in combination with Delta inverters
and DC power systems with battery backup.
Features
•
Two static switch models 6 kVA and 20 kVA
•
230 Vrms / 50 Hz single phase
•
ON LINE or OFF LINE mode selection
•
High performance AC line quality monitoring
•
Quick detection of AC faults
•
Configurable switching criteria
•
Load transfer of up to 6 kVA or 20 kVA
•
Synchronization of the Delta inverter group
•
Convection cooled
•
Compact and light
•
Power connectors on the rear
Specification
General
Product name
SSW 230 V – 6 kVA
SSW 230 V – 20 kVA
Safety
EN 60 950, class I
EMI, radiated compliant with
EN 55 022, class B
EN
300
386-2
Cooling Convection cooled
Public AC Input
Voltage range
184 ... 276 V
rms
Frequency range
45 - 55 Hz
EMI, conducted compliant with EN 55022, class B
Inverter AC Input
Voltage range
230 V
rms
± 1%
Frequency
50 Hz
EMI, conducted compliant with EN 55022, class B
AC Output
Voltage, nominal
230 V
rms
Frequency, nominal
50 Hz
Maximum power
6 kVA / 20 kVA
cosφ, range
0 .. 1 ind. and cap.
EMI, conducted compliant with EN 55022, class B
Mechanics 6kVA ; 20kVA
Width, overall
2.8” / 70 mm ; 5.3” / 135 mm
Depth, overall
13.8” / 350 mm ; 13.8” / 350 mm
Height, overall
12.2” / 311 mm ; 12.2” / 7U / 311 mm
Weight
7.7 lb / 3.5 kg ; 18.0 lb / 8.6 kg
Switching Criteria
According to
ETS 300 132-1
Static rms deviation
± 10 %
Dynamic rms deviation
± 15 % for max. 500 ms
Static freq. deviation
± 2Hz
Dynamic freq. deviation
± 2Hz for 5 s maximum
Environment
Operating temperature
0 ... + 50 °C
Relative humidity 95 % max, non condensing
The Static Switch Product Line