Warning

Always read this instruction sheet thoroughly before using DVP EH digital I/O extension unit.
This is an OPEN TYPE extension unit. The extension unit should be kept in an enclosure away from airborne, dust,

high humidity, electric shock risk and vibration. Also, it is equipped with protective methods such as special tools or
keys to open the enclosure, so as to avoid the hazard to users and damage the extension unit.

DO NOT connect AC main circuit power supply to any of the input/output terminals, as it will damage the extension

unit. Check all the wiring prior to power up. DO NOT touch terminals when power on.

Introduction

Thank you for choosing Delta DVP-EH series PLC. The main processing units offer 8 ~ 48 points and the
maximum input/output can be extended up to 256 points.

Product Profile and Outline

1

3

4

3

5

5

2

7

7

2

1

5

5

3

3

4

7

7

Dimension (mm)

Model

Length

Width

Height

DVP08HM11N

90

40

82

DVP16HM11N

90

55

82

DVP08HN11R/T

90

40

82

DVP16HP11R/T

90

55

82

3

4

2

6

6

6

7

7

3

3

8

9

1

10

11

Dimension (mm)

Model

Length

Width

Height

DVP32HN00R/T

90

143.5

82.2

DVP32HP00R/T

90

143.5

82.2

DVP48HP00R/T

90

174

82.2

1. Power, low voltage indicators

5. Extension wiring

9. Cover

2. I/O terminals

6. Extension port cover

10. Input indicators

3. DIN rail clip

7. Direct mounting holes

11. Output indicators

4. DIN rail

8. Model name

DVP EH Series Model

Input unit

Output unit

Model

Power

Points

Type

Points

Type

DVP08HM11N

8

0

DVP16HM11N

16

0

N/A

DVP08HN11R

0

8

DVP08HP11R

4

4

DVP16HP11R

8

8

Relay: 250V AC/30V DC 2A/1point

DVP08HN11T

0

8

DVP08HP11T

4

4

DVP16HP11T

24V DC

8

DC Type

Sink/Source

8

Transistor: 5 ~ 30V DC 0.3A/1point at 40°C

ENGLISH

Specifications

Electrical Specification

Model

Item

08HM11N
16HM11N

08HN11R/T 08HP11R/T 16HP11R/T 32HN00R/T

32HP00R/T

48HP00R/T

Power supply voltage

24V DC (20.4 ~ 28.8V DC) (-15% ~ 20%)

100~240V AC (-15%~10%), 50/60Hz ± 5%

Power consumption

1W/1.5W

1.5W

1.5W

2W

30VA

30VA

30VA

24V DC supply current

NA

NA

NA

NA

NA

500mA

500mA

Power protection

24V DC output with short-circuit protection

Voltage withstand

1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE)

Insulation resistance

> 5 MΩ at 500V DC (Between all input/output and earth)

Noise immunity

ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 250V,
Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m

Grounding

The diameter of grounding wire cannot be smaller than the wire diameter of the terminals Land
N (All DVP units should be grounded directly to the ground pole.)

Environment

Operation: 0

°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;

Storage: -25

°C ~ 70°C (temperature), 5 ~ 95% (humidity)

Vibration/shock
resistance

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

Weight (g)

124/160

130/120

136/116

225/210

660/590

438/398

616/576

Approvals

I/O Terminal Specification

Input point

Input point type

DC

Input type

DC (SINK or SOURCE)

Input current

24V DC 5mA
Off

→On, above 16.5V DC

Active level

On

→Off, below 8V DC

Reaction time

About 20ms

Circuit isolation
/operation indicator

Photocoupler/LED On

Output point

Output point type

Relay-R

Transistor-T

Current specification

1.5A/1point (5A/COM)

55°C 0.1A/1point, 50°C 0.15A/1point,
45°C 0.2A/1point, 40°C 0.3A/1point (2A/COM)

Voltage specification

Below 250V AC, 30V DC

30V DC

75VA (inductive)

Maximum load

90W (resistive)

9W

Reaction time

About 10ms

Off

→On 15us On→Off 25us

Input unit

Output unit

Model

Power

Points

Type

Points

Type

DVP32HN00R

0

32

DVP32HP00R

16

16

DVP48HP00R

24

24

Relay: 250V AC/30V DC 2A/1point

DVP32HN00T

0

32

DVP32HP00T

16

16

DVP48HP00T

100 ~ 240V

AC

24

DC Type

Sink/Source

24

Transistor: 5 ~ 30V DC 0.3A/1 point at 40°C

Installation and Wiring

Digital I/O Terminal Wiring

08HM

DVP-08HM (8in)

X0 X

2

X

4 X6

X

1 X3

X

5 X7

S/S

08HN

DVP-08HN (8out)

Y0 Y1

Y3

Y4 Y5

Y7

C0 Y2

C1 Y6

08HP

DVP-08HP (4in/4out)

X 0

Y1

Y 3

C0 Y2

Y0

X 2

S /S X 1 X3

16HM

DVP-16HM (16in)

X10 X 11

S /S

X1

X 3

S/S

X12 X13 X 14 X15 X16 X 17

X 0

X2

X4 X5

X7

X6

16HP

DVP-16HP (8in/8out)

X4 X5

X 1

X3

S /S

X6 X7

Y3

Y4 Y5 Y 6

X0

X 2

C 0 Y 0

Y2

Y 1

Y 7

32HN

X15

X14

C3

Y12

Y11

Y10

Y7

Y6

C2

Y5

Y4

Y3

C1

Y2

Y1

Y16

Y20

Y21 Y22 Y23

Y24

C7

C6

C5

C4

Y25

Y30

Y31

Y35

Y36

Y34

Y32

Y27

Y26

C0

DVP-32HN(32out)
(AC Power IN)

Y33

Y37

32HP

X1 7

X16

X15

X14

X13

X12

X11

X1 0

X7

X6

X5

X4

X3

X2

X1

X0

Y0

Y1

Y2

Y3

Y4

Y5

Y6

C3

C2

C1

C0

Y7

Y1 2

Y13

Y16

Y17

Y1 5

Y1 4

Y11

Y1 0

S/S

DVP-32HP(16in/16out)
(AC Power IN,DC Signal IN)

48HP

X17

X16

X15

X14

X13

X12

X11

X10

X7

X6

X5

X4

X3

X2

X1

X0

Y0

Y1

Y2

Y3

Y4

Y5

Y6

C3

C2

C1

C0

Y7

Y12

Y13

Y16

Y17

Y15

Y14

Y11

Y10

S/S

X27

X26

X25

X24

X23

X22

X21

X20

C4 Y21

Y22

Y27

Y23

Y26

Y24

Y20

Y25

DVP-48HP(24in/24out)
(AC Power IN,DC Signal IN)

Mounting Arrangements and Wiring Notes

DIN Rail Installation:
The DVP-PLC can be secured to a cabinet by using the DIN
rail that is 35mm high with a depth of 7.5mm. When
mounting the PLC on the DIN rail, be sure to use the end
bracket to stop any side-to-side motion of the PLC, thus to
reduce the chance of the wires being pulled loose. On the
bottom of the PLC is a small retaining clip. To secure the
PLC to the DIN rail, place it onto the rail and gently push up
on the clip. To remove it, pull down on the retaining clip and
gently pull the PLC away from the DIN rail. Please see the
figure on the right:

Direct Mounting: Use the specified dimensions and install with M4 screws.

For heat dissipation. Make
sure to provide a minimum
clearance of 50mm between
the unit and all sides of the
cabinet. (shown as below)

D V P MP U

> 5 0 mm

> 5 0mm

> 5 0 mm

> 5 0 mm

Wiring:

Below 6.2

To suit M3.5 screw terminal

Below 6.2

1. Please use O-type or Y-type terminals for I/O wiring terminals. The

specification for the terminals is as shown on the left. PLC terminal screws
should be tightened to between 5 ~ 8 kg-cm (4.3 ~ 6.9 in-lbs). Use copper
conductor only, 60°C/75°C.

2. DO NOT wire to the No Function terminals

• . I/O signal wires or power

supply should not run through the same multi-wire cable or conduit.

3. When tightening the screws and performing wiring, please avoid that

metallic particles fall into PLC. After completing wiring, please remove the
label which is used to obstruct the metallic particles on the ventilation hole
for well heat dissipation.

4. There should be a 50mm or more distance between the PLC and other

control component. Also, keep the PLC away from high voltage line and
power equipment.

Environment:

1.

DO NOT store the PLC in an airborne dust, smoky, metallic particles, corrosive or flammable gases.

2. DO NOT store the PLC in a location where temperatures and humidity will exceed specification.
3. DO NOT mount the PLC in a location where vibration and shock will exceed specification.

I/O Point Serial Sequence

When connecting MPU with less than 32 points to extension unit, the input number of 1

st

extension unit is

started from X20 in sequence and the output number is started from Y20 in sequence. If connecting MPU with
more than 32 points to extension unit, the input number of the 1

st

extension unit is started from the last input

number of the MPU in sequence and the output number is started form the last output number of the MPU in
sequence.

MP U

EXT 1 EXT 2 EXT3 EXT 4

PLC

Model

Input

points

Output

points

Input number

Output number

MPU 16EH/32EH/64EH 8/16/32

8/16/32 X0~X7/X0~X17/X0~X37

Y0~Y7/Y0~Y17/Y0~Y37

EXT1

32HP

16

16

X20~X37/X20~X37/X40~X57

Y20~Y37/Y20~Y37/Y40~Y57

EXT2

48HP

24

24

X40~X67/X40~X67/X60~X107

Y40~Y67/Y40~Y67/Y60~Y107

EXT3

08HP

4

4

X70~X73/X70~X73/X110~X113

Y70~Y73/Y70~Y73/Y110~Y113

EXT4

08HN

0

8

-

Y74~Y103/Y74~Y103/Y114~Y123

In system application example, if the input/output of the 1

st

MPU are less than 16, its input/output will be defined

as 16 and thus there are no corresponding input/output for higher numbers. The input/output number of
extension number is the sequential number from the last number of the MPU.

Power Input Wiring and Specification

The power input for DVP-EH series PLC is AC input. Please pay particular attention to the following notes:
1. Connect the AC input (100 ~ 240V) to terminals L and N. Any 110V AC or 220V AC connected to the +24V

terminal or input points will permanently damage the PLC.

2. The AC power inputs for the MPU and the I/O Extension Unit should be ON or OFF at the same time.
3. Please use wires of 1.6mm or above for the grounding of the MPU.
4. If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too long or

the power voltage drops, the PLC will stop operation and all outputs will be off. Once power is on again, the
PLC will resume automatically. (There are latched auxiliary relays and registers inside of the PLC, please be
aware when programming.)

AC Input

Type

L

N

2.0 A

DC/DC

+5V

+24V

24G

S/S

X0

X1

X2

100~240VAC

The +24V supply output is rated at 0.5A as max. from MPU. DO NOT connect external power
supply to this termianl. Moreover, it takes 6 ~ 7mA to drive each input point, so total of 100mA
is needed for 16 input points. As a result, the output load of +24V should not exceed 400mA.

Since the PLC is in control of numerous devices, operation of either one device could affect the operation of
other devices; therefore, the breakdown of either one device would consequently be detrimental to the whole
auto control system, and danger will thus be resulted. Please use the recommended wiring below for the power
input:

Power supply for AC loads

Fuse for circuit protection (3A limit)

Power on pilot indicator

Emergency stop: a manual stop button is provided for emergency
to disconnect system power.

Circuit isolation device (System Power Disconnect): use
electromagnetic contactor and the relay to be the isolation unit of
the power circuit to prevent the possible instability of the system
when the power is supplied on and off.

DVP PLC MPU (main processing unit)

Class three grounding.

OV

24 VDC

MC

MC

N

L

1

1

2

3

4

5

6

6

7

8

Guard
Lim it

Power supply:

AC: 100 ~ 240V AC, 50/60Hz
DC: 24V DC

Input/Output Point Wiring

Input Point Wiring
There are SINK and SOURCE types for the input signal of the input point with DC input. Definition as follows:

Sink = Current flow into common terminal S/S

Source = Current flows out of common terminal S/S

S/S

X0

Sinking

S/S

X0

Sourcing

Input point loop equivalent circuit

Wiring loop

DC Type

(DC Signal IN)

SINK Mode

(Current flows into the
common terminal S/S)

24VDC

24G

X0

S/S

+24V

SINK

+5V

24G

S/S X0

X1

X2

+24V

Sink Type

Input point loop equivalent circuit

Wiring loop

DC Type

(DC Signal IN)

SOURCE Mode

(Current flows out of

common terminal S/S)

24VDC

24G

X0

S/S

+24V

SOURCE

+5V

24G

S/S X0

X1

X2

+24V

Source Type

Output Point Wiring

DO NOT wire to the No Function terminals

Fuse

Diode in reverse direction to protect the relay*1

Mutually exclusive outputs*2

Emergency stop: use an external switch

Surge absorber*3

Conductive loading

Incandescent lamp (resistive loading)

DC supply

Relay output wiring

MC2

MC1

9

10

C0

C1

Y0

Y4

C2

Y2

Y3

Y5

Y1

5

2

3

7

8

1

6

7

2

5

4

MC2

MC1

AC supply

*1: There is no protection circuit for the Relay output in the PLC. If DC conductive loading is on, add a diode in reverse direction in

parallel to extend the life of the Relay. The diode in reverse direction should correspond to the following specification:

- The diode is able to withstand 5~10+ times loading voltage as maximum.

- The forward current of the diode must be greater than loading current.

*2: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection.
*3: There is no protection circuit for the Relay in the PLC. If AC conductive loading is on, connect a surge absorber (0.1uF+ “100ohm to

120ohm”) to reduce interference and extend the life of the Relay.

DO NOT wire to the No Function terminals

Emergency stop

Fuse

Mutually exclusive output*1

DC apply

Incandescent lamp (resistive loading)

Diode in reverse direction to protect the transistor*2

Conductive loading

Transistor output wiring

MC2

MC1

C0

C1

Y0

Y4

C2

Y2

Y3

Y5

Y1

5

7

8

1

6

6

4

MC2

MC1

2

3

3

9

Resistive loading

*1: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection.
*2: Use Zener diode (39V) inside the PLC to protect the transistor. If conductive loading is on, adding a diode in reverse direction in

parallel is recommended.

注意事項

請在使用之前,詳細閱讀本使用說明書。

本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊

意外之外殼配線箱內。另必須具備保護措施 (如: 特殊之工具或鑰匙才可打開) 防止非維護人員操作或意外衝

擊本體,造成危險及損壞。

交流輸入電源不可連接於直流類型之輸入/出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認

電源配線。請勿在上電時觸摸任何端子。

產品簡介

謝謝您採用台達 DVP-EH 可程式控制器。EH 8 ~ 48 點擴充,含主機最大數位輸入/輸出擴充分別可達 256 點。

產品外觀及各部介紹

1

3

4

3

5

5

2

7

7

2

1

5

5

3

3

4

7

7

尺寸 (mm)

機種名稱

DVP08HM11N

90

40

82

DVP16HM11N

90

55

82

DVP08HN11R/T

90

40

82

DVP16HP11R/T

90

55

82

3

4

2

6

6

6

7

7

3

3

8

9

1

10

11

尺寸 (mm)

機種名稱

寬 (w)

DVP32HN00R/T

90

143.5

82.2

DVP32HP00R/T

90

143.5

82.2

DVP48HP00R/T

90

174

82.2

1.

電源、低電壓指示燈

5.

擴充排線

9.

上蓋

2.

輸出/入端子

6.

擴充機連接口上蓋

10.

輸入指示燈

3. DIN

軌固定扣

7.

直接固定孔

11.

輸出燈示燈

4. DIN

軌固定槽

8.

機種名稱

機種型號

輸入單元

輸出單元

機種

電源

點數

形式

點數

形式

DVP08HM11N

8

0

DVP16HM11N

16

0

DVP08HN11R

0

8

DVP08HP11R

4

4

DVP16HP11R

8

8

繼電器 Relay 250V AC/30V DC 2A/1 點

DVP08HN11T

0

8

DVP08HP11T

4

4

DVP16HP11T

24V DC

8

DC Type

Sink/Source

8

電晶體 Transistor 5 ~ 30V DC 0.3A/1 點
@40°C

繁體中文

輸入單元

輸出單元

機種

電源

點數

形式

點數

形式

DVP32HN00R

0

32

DVP32HP00R

16

16

DVP48HP00R

24

24

繼電器 Relay 250V AC/30V DC 2A/1 點

DVP32HN00T

0

32

DVP32HP00T

16

16

DVP48HP00T

100 ~ 240V

AC

24

DC Type

Sink/Source

24

電晶體 Transistor 5 ~ 30V DC 0.3A/1 點
@40

°C

規格

電氣規格

機種

項目

08HM11N
16HM11N

08HN11R/T 08HP11R/T 16HP11R/T 32HN00R/T 32HP00R/T 48HP00R/T

電源電壓

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ 20%)

100 ~ 240V AC (-15% ~ 10%),
50/60Hz ± 5%

消耗電力

1W / 1.5W

1.5W

1.5W

2W

30VA

30 VA

30 VA

24V DC

供應電流

NA

NA

NA

NA

NA

500 mA

500 mA

24V DC

輸出具短路保護

24V DC

輸出具短路保護

突波電壓耐受量

1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE)

絕緣阻抗

5 MΩ

以上(所有輸出/入點對地之間 500V DC)

雜訊免疫力

ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 250V,
Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m

接地

接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地)

操作/儲存環境

操作:0 ~ 55°C(溫度), 50 ~ 95%(濕度), 污染等級 2

儲存:-25 ~ 70°C(溫度),5 ~ 95%(濕度)

耐振動/衝擊

國際標準規範 IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

重量(約)(g)

124/160

130/120

136/116

225/210

660/590

438/398

616/576

認證

輸入/出點規格

輸入點電氣規格

輸入點形式

直流

輸入形式

直流(SINK 或 SOURCE)

輸入電壓電流

24V DC 5mA

Off → On 16.5V DC

以上

動作位準

On → Off 8V DC

以下

反應時間

約 20ms

電路隔離/操作指示

光耦合器/LED On

輸出點電氣規格

輸出點形式

繼電器-R

電晶體-T

電流規格

1.5A/1

點(5A/COM)

55°C 0.1A/1

點、50°C 0.15A/1 點、

45°C 0.2A/1

點、40°C 0.3A/1 點(2A/COM)

電壓規格

250V AC,30V DC

以下

30V DC

75VA

(電感性)

最大負載

90 W

(電阻性)

9W

反應時間

約 10 ms

Off → On 15us

On → Off 25us