Delta Electronics Modbus TCP Remote I/O Communication Module RTU-EN01 User Manual

Page 27

background image

Modbus TCP Remote I/O Communication Module RTU-EN01

DVP-PLC Operation Manual

25

You can move the IF-THEN setting upwards or downwards to change the execution order of them.

6.8 Smart PLC Setting: Timer

RTU-EN01 has the independent Smart PLC function. The timer is able to time following the system time. There

are 16 timers in RTU-EN01. The timing range is 10ms ~ 655,35s.

„

Timer

1. Enable:

Decide whether to enable the timer in this column.

2. Cyclic:

Decide whether to reset the timer and re-start the timing when the timing reaches the target in this

column.

3. Reset

when

STOP->RUN:

Decide whether to reset the timer when the system goes from STOP to RUN.

4. Timeout

bound:

The time for the timer to reach the target. Range: 10ms ~ 65,535s.

6.9 Smart PLC Setting – Counter

RTU-EN01 has the independent Smart PLC function. The counter can be triggered by the external input points

RX. When RX turns from OFF to ON, the counter will start to count. There are 16 counters in RTU-EN01,

responsible for counting up and counting down. The counting range is -32,768 ~ 32,767.

„