Delta Electronics Terminal Panels Series TP02G-AS1 User Manual
Warning, Introduction, Specifications
Warning
Please read this instruction carefully before use.
Switch off the power before wiring.
The display panel of TP02 series is waterproof. But please prevent grease, corrosive liquids and sharp objects from
contacting the TP02 series.
The TP02 series require 24V DC input power. DO NOT connect input AC power supply to any of the RS-485
communication port; otherwise serious damage may occur. Check all the wiring again before switching on the
power.
DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after
the power is switched off.
Make sure the groud terminal
is correctly grounded in order to prevent electromagnetic interference.
Please use the fixed support accessory which is packed together with the product provided by Delta. DO NOT
tighten the screws out of the normal torque specifications; otherwise serious damage may occur.
Introduction
Product Outline
Displaying Area
RS-232 LED Indicator
RS-485 LED Indicator
Escape / Exit Key
Alarm LED Indicator
Function Keys
Arrow Keys
Enter Key
Panel Function Explanation
Panel component
Explanation
Alarm LED
indicator (RED)
Status 1: When power is on, LED will blink slowly for three times.
Status 2: When there is an abnormal situation, LED will blink quickly along with an alarm sound.
RS-232 LED
indicator (yellow)
LED will blink when transmits program and communicates via RS-232.
RS-485 LED
indicator (green)
LED will blink when communicates via RS-485.
Displaying area
Liquid Crystal Module display area. It is used to display current program status.
Escape/Exit key
It is used to cancel an incorrect input, or to exit a programming step.
Enter key
It is used to input a value or accept a programming command.
Arrow keys
UP/Pg Up: It is used to increase the value or move up one page.
Pg Dn/DOWN: It is used to decrease the value or move down one page.
Left: This key is left direction key and it can be used to select the position of the value.
Right: This key is right direction key and it can be used to select the position of the value.
Function keys
F0/0: It is used as a constant 0, or the user can define it as function F0.
F1/1: It is used as a constant 1, or the user can define it as function F1.
F2/2: It is used as a constant 2, or the user can define it as function F2.
F3/3: It is used as a constant 3, or the user can define it as function F3.
F4/4: It is used as a constant 4, or the user can define it as function F4.
F5/5: It is used as a constant 5, or the user can define it as function F5.
F6/6: It is used as a constant 6, or the user can define it as function F6.
F7/7: It is used as a constant 7, or the user can define it as function F7.
F8/8: It is used as a constant 8, or the user can define it as function F8.
F9/9: It is used as a constant 9, or the user can define it as function F9.
ENGLISH
Back Panel
RS-232
Extension port
5 PIN terminal/Wire gauge: 12-24 AWG/Torque: 4.5 lb.-inch
Dimension
Front panel (unit: mm [inch])
Right side diagram (unit: mm [inch])
Vertical view (unit: mm)
Mounting dimension (unit: mm [inch])
Thickness Range 0.5~9mm
135~136.5[5.31~5.37]
85
[3.35]
Installation
Please insert TP02 series to the opening hole of panel and tighten the screws. However, if a firm mounting
TP02 series to the panel is needed, please use the mounting fixed support accessory which is packed together
with TP02 series, then insert the fixed support in the back and tighten the screws.
If the fixed support is not installed well, Delta will not guarantee the waterproof function. The screw torque
should be 4-5(kg-cm). DO NOT exceed this specification when tightening the screws; otherwise TP02 series
may be damaged. Please leave sufficient space (more than 50mm) around the unit for heat dissipation.
Notes: The flat surface should be a UL Type 4 "Indoor Use Only" enclosure or equivalent (IP65/NEMA4). Please refer to
the figures below.
Thickness: 0.5~9.0mm
Specifications
Function Specifications
Item
TP02G-AS1
Screen type
STN-LCD
Display color
Monochromatic
Backlight
The back-light automatic turn off time is 1 ~ 99 minutes (0 = DO NOT turn off)
(The back-light life is about 50 thousand hours at 25°C)
Resolution
160 x 32 dots
5×8 dots, 25 characters×8 rows
8×8 dots, 16 characters×8 rows
8×12 dots, 16 characters×5 rows
8×16 dots, 16 characters×4 rows
Display range
(W) x (H) = 72 x 22 (unit: mm)
Contrast adjustment
15 levels of adjustment
Language/font
ASCII: Alphanumeric (including European characters)
Taiwan: (Big 5 codes) Traditional Chinese Fonts
China: (GB2324-80 codes) Simplified Chinese Fonts
Font size
ASCII: 5 Ч 8, 8 Ч 8, 8 Ч 12, 8 Ч 16
Alarm LED indicator
(RED)
1. Power on indication (blink for three times)
2. Communication error alarm
3. Special indication by user programming
RS-232 LED
indicator (yellow)
It will blink when transmitting program and communicating by using RS-232.
Display
screen
RS-485 LED
Indicator (green)
It will blink when communicating by using RS-485.
Program memory
256KB flash memory
RAM of system
32K Byte
Serial
communication port
RS-232 (COM1)
Unsynchronized transmission method: RS-232
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits
Parity: none/odd/even, Transmission speed: 4,800 bps ~115,200 bps
RS-232: 9 PIN D-SUB male
Extension
communication port
RS-485 (COM2)
Unsynchronized transmission method: RS-485
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits
Parity: None/Odd/Even, Transmission speed: 4,800 bps ~115,200 bps
RS-485: 5 PIN removal terminal
Extension interface
1. Update firmware version
2. The slot for program copy card
External
interface
5 PIN removal
terminal
Include 24V DC input and RS-485 communication input
Electrical Specifications
Specifications
TP02G-AS1
Communication interface
COM1: RS-232 COM2: RS-485
Waterproof class of front panel
IP65/NEMA4
Operating temperature for
hardware
0 ~ 50°C; 20 ~ 90%RH (non-condensing)
Specifications
TP02G-AS1
Storage temperature for
hardware
-20 ~ 60°C
Vibration
5Hz f
≦ <9Hz = Continuous: 1.75mm / Occasional: 3.5mm
9Hz
f
150Hz = Continuous: 0.5g / Occasional: 1.0g
≦ ≦
Shock
15g peak, 11ms duration, half-sine, three shocks in each direction per axis,
on 3 mutually perpendicular axes (total of 18 shocks)
Radiated emission
CISPR11, Class A
Electrostatic discharge immunity EN61000-4-2
Radiated immunity
EN61000-4-3
Electrical fast transient
EN61000-4-4
Weight/dimensions
0.24kg; 147 Ч 97 Ч 35.5mm (Width(W) × Height(H) × Deep(D))
Cooling method
Natural air cooling
Password Function
1. If the user forgot the password, the password can be cleared by using the following code:
8888
. This
universal code will clear the password and all TP02 series internal programs. The TP02 series will be reset to
the factory settings by using this code also. Please pay close attention when using it.
2. The password can be the alphabet from A to Z or the number from 0 to 9. But it must use the function keys F0
~ F9 to input the password characters. Please refer to the following table.
F0: scrolls in a loop as follows 0→A→B→C→D→E→F→0.
F1: scrolls in a loop as follows 1→G→H→I→J→K→1.
F2: scrolls in a loop as follows 2→L→M→N→O→P→2.
F3: scrolls in a loop as follows 3→Q→R→S→T→U→ V→3.
F4: scrolls in a loop as follows 4→W→X→Y→Z→4.
F5: It just can be used to be constant 5.
F6: It just can be used to be constant 6.
F7: It just can be used to be constant 7.
F8: It just can be used to be constant 8.
F9: It just can be used to be constant 9.
Hardware Operation
When the user wants to startup TP02 series, a 24V DC power is needed. After applying 24V DC power to TP02
series, it will enter into the startup display and then enter the user-designed program. Pressing Esc key and
holding on for 5 seconds can return to system menu. There are five selections in the system menu and are
described below.
Selections
Explanation
Download
program
Use the connection cable (DVPACAB530) to connect the TP02 serial communication port RS-232 to a
PC. Then use the TPEditor software to download an application program to TP02.
Upload program
Use the connection cable (DVPACAB530) to connect the TP02 serial communication port RS-232 to a
PC. Then use the TPEditor software to upload an application program from TP02.
Copy program
Transfer a program between two TP02 units.
1: transmit programs; 2: receive programs.
When transmit programs and data between two TP02 units. Set one TP02 to “Receive Program”
mode and the other TP02 to “Transmit Program” mode. Please use twisted pair wires to connect the
two units via the RS-485 ports.
Selections
Explanation
TP02 settings
There are 8 items that used to modify TP02 system settings:
1. Communication protocol: Setting the address of TP02, the control port of PLC, and the
communication string for either RS-232 or RS-485.
2. Contrast: Adjust the contrast of LCM display screen.
3. Back-light: adjust the automatic turn off time of LCM. Setting range is 00 ~ 99 minutes. If set to 00,
the LCM Back-light will not turn off.
4. Buzzer: Used to set the buzzer sound, normal mode or quiet mode.
5. Language setting: Used to set the displayed language. English, Traditional Chinese, Simplified
Chinese or user defined language.
6. Password setting: Used to set, enable, and disable the password function. If the password function
is enabled, it will require the user to input a password before entering any system menu. The
factory password is 1234.
7. Startup display: Used to select the TP02 startup display. User can select “user defined” to use the
file that designed by TPEditor and download to TP02.
8. Comm. indicator: The user can determine if the RS-232 and RS-485 LEDs will blink or not during
communication.
PLC connection
There are two methods to connect to PLC:
1. Using TP02 serial communication port (COM1) RS-232: set 8-pin DIP switch to RS-485 mode and
connect the cable (DVPACAB215 or DVPACAB230) to program communication I/O RS-232C of
PLC.
2. Using extension communication port (COM2) RS-485: set 8-pin DIP switch to RS-485 mode and
connect 5-pin removal terminal of extension communication port to RS-485 of PLC with twisted
pair.
Execution
Execute the internal program that download from TPEditor or transmitted from other TP02 units.
When program is in execution, the user can return to system menu by pressing Escape/Exit (Esc) key
for 5 seconds.
Communication Connection
TP02G may connect to a PC by using connection able DVPACAB515
PC or TP02 / 04G
1
5
6
9
9 PIN D-SUB
TO PC (RS-232)
TO TP02 / 04G
5
1
9
6
9 PIN D-SUB
9 PIN D-SUB female
Rx
2
GND 5
5 GND
PC COM Port
9 PIN D-SUB female
3
Tx
2
Rx
TP02 / 04G COM Port
Tx
3
TP02G may connect to a DVP-PLC by using connection cable DVPACAB215/DVPACAB230/
DVPACAB2A30
DVPACAB215/DVPACAB230
TO P C o r TP 02 / 04 G
1
13
14
1
5
6
9
25 P IN D- S UB
9 P IN D- SU B
TO P LC
M INI DIN TER MIN AL
DVPACAB2A30
TO PC or TP02 / 04G
1
5
6
9
9 PIN D-SUB
TO PLC
MINI DIN TERMINAL
8 PIN M INI D IN
25 PIN D-SU B fem ale
PC / TP CO M Port
PLC CO M1 Por t
Tx
2
GN D
7
8 PIN MIN I DIN
9 P IN D -SUB female
PC / TP C O M Port
PLC CO M1 Por t
R x
2
GN D 5
6
8
20
4
5
1
4
6
7
8
4 R x
8 G ND
1,2 5V
1
2
3
4
5
6
7
8
5 Tx
Rx 3
Tx 3
1
2
3
4
5
6
7
8
4 R x
8 G ND
1,2 5V
5 Tx
注意事項
請在使用之前,詳細閱讀本使用說明書。
實施配線,務必關閉電源。
本機顯示操作面板防水,但對油污或具腐蝕性之液體不具防護作用,避免以尖銳之物品刮傷面板使用時請注
意。
本機輸入電源為直流 24V,不可連接於 RS-485 通訊口信號端,否則可能造成嚴重的損壞,因此請在上電之前
再次確認電源配線。
輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。請勿在上電時觸摸任何端子。
本體上之接地端子 務必正確的接地,可提高產品抗雜訊能力。
利用原廠包裝附件之固定架,鎖緊面板固定螺絲時,請勿太緊以免造成機殼損壞。
產品簡介
產品外觀及各部介紹
LC M
顯示區
R S-23 2
指示燈
退出 取消鍵
/
命令操作鍵
數值鍵及功能鍵
輸入鍵
警示指示燈
R S-48 5
指示燈
面板功能說明
面板元件
說明
警示指示燈(紅燈)
狀態一:當啟動電源時,指示燈慢慢開始閃爍三次。
狀態二:當異常狀態發生,指示燈會重覆持續亮一秒並發出警報聲。
RS-232
指示燈(黃燈)
傳送程式及使用 RS-232 通訊時持續閃爍。
RS-485
指示燈(綠燈)
使用 RS-485 通訊時持續閃爍。
退出/取消鍵
輸入值錯誤時可按此鍵,刪除文字敘述等。
命令操作鍵
UP/Pg Up
:此鍵為向上方向鍵,可作為數值遞增輸入或換至上頁等操作。
Pg Dn/DOWN
:此鍵為向下方向鍵,可作為數值遞減輸入或換至下頁等操作。
Left
:此鍵為左方向鍵,可作為選擇數值位置操作。
Right
:此鍵為右方向鍵。可作為選擇數值位置操作。
輸入鍵
當輸入值確認正確無誤時,即可按下此鍵。
數值鍵及功能鍵
F0/0
:可作為 0 的常數輸入鍵,也可由使用者定義其個別功能 F0。
F1/1
:可作為 1 的常數輸入鍵,也可由使用者定義其個別功能 F1。
F2/2
:可作為 2 的常數輸入鍵,也可由使用者定義其個別功能 F2。
F3/3
:可作為 3 的常數輸入鍵,也可由使用者定義其個別功能 F3。
F4/4
:可作為 4 的常數輸入鍵,也可由使用者定義其個別功能 F4。
F5/5
:可作為 5 的常數輸入鍵,也可由使用者定義其個別功能 F5。
F6/6
:可作為 6 的常數輸入鍵,也可由使用者定義其個別功能 F6。
F7/7
:可作為 7 的常數輸入鍵,也可由使用者定義其個別功能 F7。
F8/8
:可作為 8 的常數輸入鍵,也可由使用者定義其個別功能 F8。
F9/9
:可作為 9 的常數輸入鍵,也可由使用者定義其個別功能 F9。
繁體中文
背面介紹
擴充槽
RS-232
5-Pin
端子座 / 線徑:12-24 AWG / 扭力:4.5 lb-inch
外觀尺寸
正面圖 (單位:mm)
97.00 [3.82]
147.00 [5.79]
俯視圖 (單位:mm)
3.50 [0.14]
30.50 [1.20]
135.05 [5.31]
40.50 [1.59]
嵌入開孔尺寸 (單位:mm)
右側圖 (單位:mm)
85.00 [3.35]
安裝方式
人機介面安裝於控制盤的方法,請直接將人機由盤面的正面直接放入即可(嵌入式),若要固定更牢固,可再利
用原廠包裝附件之固定架,嵌入後蓋直接四端凹槽處固定,並上、下平均鎖緊面板固定螺絲即可,如下圖為正確
安裝:( 固定螺絲時請以扭力:4-5 (kg-cm) 鎖緊,請勿超過此範圍以免破壞面板)
注意:該安裝的平面必須是要適用 Type 4 室內使用或相等條件的配電盤外殼。