7.17 Smart PLC: Counter

Application Setting up the counter by DCISoft. Once RX#1 counts for 5 times, RY0 will output.

Steps

(1) Set up counter C0: RX#1 counts up 5 times and reaches the target.
(2) Set up IF-THEN: When the counting reaches the target, RY0 will output.

1. Open the setup page and switch to “Smart PLC” page. Further switch to the “Counter” page.

2. Check to “Enable” Counter 0, select “Count Up”, set Up Bound to “5” and Count Source RX NO. to RX”1”.

Click "Apply” to write these settings into RTU-EN01.

3. Switch to “IF-THEN” page and check the “Enable” box. Select “C 0 On” in the IF column and “RY 0 Set” in

the THEN column. Click on “Add” to add the settings to the table below and press “OK” to save the settings

into RTU-EN01.