11 stroke characterization – Flowserve 400MD Logix User Manual
Page 94

40
93.4
9..57
40
45
94.2
11.86
45
50
94.8
14.15
50
55
95.5
17.54
55
60
96.0
20.93
60
65
96.5
25.94
65
70
97.0
30.95
70
75
97.5
38.36
75
80
98.0
45.77
80
85
98.5
55.66
85
90
99.0
67.68
90
95
99.5
82.31
95
100
100.0
100.0
100
NOTE: Custom characterization points can only be entered with the FB configurator.
Figure 10.3 Logix 3400MD Digital Positioner Characteristic Curves
10.11 Stroke Characterization
In addition to three pre-defined and embedded characterization curves, the Logix 3400MD positioner has a 21-point custom stroke characterization feature.
This allows the user to define a unique set of operating parameters customizable to his process conditions.
Table 10.15 Transducer Block Characterization Parameters
Parameter
Description
Value — Meaning
Comments
MODE_BLK
The operating mode of the
transducer block
Permitted Modes: Auto - Auto (tar-
get mode) OOS - Out of Service
The transducer block must be out-of-service before
the user can edit or change characterization.
CONTROL_FLAGS
Byte values which select posi-
tioner operation features
1 Quick Opening Curve*
Loads factory defined QO curve as custom curve.
2 Equal Percent Curve
Loads factory defined equal percent curve as custom
curve.
4 Positioner Model
5 Actuator Style
6 Custom Characterization Active
Activates custom curve. If Off, response is Linear.
8 Air Action
CURVEX
Numeric X value array for cus-
tom point. (1x21 array points)
X-axis value for custom stroke char-
acterization point. Range -10 to 110
Pair each X-value with corresponding Y-value to
define the desired point. Values must be in ascending
(or equal) order.
CURVEY
Numeric Y value array for cus-
tom point. (1x21 array points)
Y-axis value for custom stroke char-
acterization point. Range -10 to 110
0
10
20
30
40
50
60
70
80
90
100
Linear
Equal Percent
Quick Open
0
20
40
60
80
100
FINAL_VALUE (% FS)
CMD_USED (% FS)
Logix 3400MD Digital Positioner LGENIM3405-02 11/13
94