6 tech transducer block – Flowserve 400MD Logix User Manual
Page 39
Signatures See Section 10.13, Initiating a Valve Signature for more details on using the signature acquisition functions of the Logix 3400MD digital
positioner.
Custom Characterization See Section 10.11, Stroke Characterization for more details on using the custom characterization features of the Logix 3400MD
digital positioner.
8.6 Tech Transducer Block
The Tech Transducer block contains the parameters used by a technician to troubleshoot a positioner. Many of these parameters are not up-
dated on a regular basis. In order to cause these parameters to update on a regular basis the TEST_MODE parameter in the Main Transducer
block must have the diagnostics enabled.
Section 10.16 Lists the parameters that do not update unless TEST_MODE is selected.
Table 8.7 Tech Transducer Block Parameters
Index
Origin
Name
Store
Date Type
Default Value
0STND XDTB_TECH
SRW Record
BLOCK
0
1STND ST_REV
SR
Simple
UNSIGNED16
1
2STND TAG_DESC
SRW Simple
OCTET_STRING
“7 “
3STND STRATEGY
SRW Simple
UNSIGNED16
2
4STND ALERT_KEY
SRW Simple
UNSIGNED8
4
5STND MODE_BLK
SRW Record
MODE
0x01;0x01;0x11;0x10
6STND BLOCK_ERR
R
Simple
BIT_STRING
0
7STND UPDATE_EVT
RW Record
ALARM_EVENT
0;0;0,0;0;0;0;0
8STND BLOCK_ALM
RW Record
ALARM_DISC
0;0;0,0;0;0;0;0;0;0
9STND TRANSDUCER_DIRECTORY
NR
Array
UNSIGNED16
0
10STND TRANSDUCER_TYPE
NR
Simple
UNSIGNED16
106
11STND XD_ERROR
R
Simple
UNSIGNED8
0
12STND COLLECTION_DIRECTORY
NR
Array
UNSIGNED32
0
13MFG
ELECTRONIC_STATUS
R
Simple
BIT_STRING
0
14MFG
ELECTRONIC_MASKING
NRW Simple
BIT_STRING
0
15MFG
INNERLOOP_STATUS
R
Simple
BIT_STRING
0
16MFG
INNERLOOP_MASKING
NRW Simple
BIT_STRING
0
17MFG
OUTERLOOP_STATUS
R
Simple
BIT_STRING
0
18MFG
OUTERLOOP_MASKING
NRW Simple
BIT_STRING
0
19MFG
CONFIGURATION_STATUS
R
Simple
BIT_STRING
0
20MFG
CONFIGURATION_MASKING
NRW Simple
BIT_STRING
0
21MFG
PRESSURE_STATUS
R
Simple
BIT_STRING
0
22MFG
PRESSURE_MASKING
NRW Simple
BIT_STRING
0
23MFG
DEVIATION_EFFORT
R
Simple
FLOATING_POINT
0
24MFG
PRESS_CTRL_EFFORT
R
Simple
FLOATING_POINT
0
25MFG
INTEGRAL_EFFORT
R
Simple
FLOATING_POINT
0
26MFG
SPOOL_OFFSET
RW Simple
FLOATING_POINT
0
27MFG
SPOOL_COMMAND
RW Simple
FLOATING_POINT
0
28MFG
BACKOFF_EFFORT
R
Simple
FLOATING_POINT
0
29MFG
SPOOL_POSITION
R
Simple
FLOATING_POINT
0
30MFG
SPOOL_EFFORT
R
Simple
FLOATING_POINT
0
31MFG
PIEZO_OFFSET
R
Simple
FLOATING_POINT
0
32MFG
PIEZO_COMMAND
R
Simple
FLOATING_POINT
0
33MFG
USER_INTERFACE_INSTANT
R
Simple
BIT_STRING
0
34MFG
USER_INTERFACE_ACTIVE
RW Simple
BIT_STRING
0
35MFG
P_GAIN_EFFECTIVE
R
Simple
FLOATING_POINT
0
36MFG
P_GAIN_MULT
SRW Simple
FLOATING_POINT
0.05
Logix 3400MD Digital Positioner LGENIM3405-02 11/13