NOTE: SIMULATE.ENABLE can only be set TRUE when the Simulate dip switch is in the “On” position when the device is powered up or a pro-
cessor restart is issued.
READBACK Parameter The value and status of READBACK will come from either the OUT parameter or SIMULATE.SIMULATE, determined by
the state of the OUT_READBACK feature in the Resource Block. READBACK is in XD units.
When RS.FEATURE.OUT_READBACK is set TRUE, SIMULATE.SIMULATE is used for READBACK. When FEATURE.OUT_READBACK is FALSE, OUT
will be used for READBACK.
NOTE: The default value for RS.FEATURE.OUT_READBACK is FALSE. With the Logix 3400MD, this feature should always be set TRUE to allow
the transducer block position value to be the source of READBACK.
READBACK_OUT ALLOWS THE USER A LINKABLE PARAMETER FOR VALVE POSITION.
PV Parameter The PV value is simply the READBACK value, re-scaled from XD units to PV units. PV status is copied directly from READBACK
status.
8.9 Digital Output Function Block
DO Block Description
Operates according to Section 10.18
Table 8.10 DO Function Block Parameter List
Index Origin
Name
Store
Date Type
Default Value
0
STND DISCRETE_OUTPUT_BLOCK
SRW
Record
BLOCK
0
1
STND ST_REV
SR
Simple
UNSIGNED16
0
2
STND TAG_DESC
SRW
Simple
OCTET_STRING
“ “
3
STND STRATEGY
SRW
Simple
UNSIGNED16
0
4
STND ALERT_KEY
SRW
Simple
UNSIGNED8
0
5
STND MODE_BLK
SRW
Record
MODE
0x01;0x01;0x79;0x30
6
STND BLOCK_ERR
R
Simple
BIT_STRING
0
7
STND PV_D
R
Record
DISC_S
0;0
8
STND SP_D
NRW
Record
DISC_S
DO_VAL_SP_D_STATUS;DO_VAL_SP_D_VALUE
9
STND OUT_D
NRWO Record
DISC_S
0x1C;0
10 STND SIMULATE_D
RW
Record
SIM_DISC
0;0;0;0;1
11 STND PV_STATE
SRW
Simple
UNSIGNED16
0
12 STND XD_STATE
SRW
Simple
UNSIGNED16
0
13 STND GRANT_DENY
RW
Record
ACCESS_PERM
0;0
14 STND IO_OPTS|IO_OPTS_DO
SRW
Simple
BIT_STRING
0
15 STND STATUS_OPTS|STATUS_OPTS_DO
SRW
Simple
BIT_STRING
0
16 STND READBACK_D
R
Record
DISC_S
0;0
17 STND CAS_IN_D
RWI
Record
DISC_S
0x1C;0
18 STND CHANNEL
SRW
Simple
UNSIGNED16
0
19 STND FSTATE_TIME
SRW
Simple
FLOATING_POINT
0
20 STND FSTATE_VAL_D
SRW
Simple
UNSIGNED8
0
21 STND BKCAL_OUT_D
RO
Record
DISC_S
0;0
22 STND RCAS_IN_D
RW
Record
DISC_S
0x1C;0
23 STND SHED_OPT
SRW
Simple
UNSIGNED8
0
24 STND RCAS_OUT_D
R
Record
DISC_S
0;0
25 STND UPDATE_EVT
RW
Record
ALARM_EVENT
0;0;0,0;0;0;9;0
26 STND BLOCK_ALM
RW
Record
ALARM_DISC
0;0;0,0;0;0;0;8;0;0
Block
Logix 3400MD Digital Positioner LGENIM3405-02 11/13