10 digital input function block, 11 input selector function block, Di block description – Flowserve 400MD Logix User Manual
Page 48: Is block description

The functionality of these parameters follows the standard Fieldbus definitions as defined in the Foundation Fieldbus specifications.
8.10 Digital Input Function Block
DI Block Description
The DI block takes the manufacturer’s input data, selected by channel number, and makes it available to other function blocks at its output.
This block operates according to the Foundation Fieldbus specifications. Also found in Section 10.19
Table 8.11 DI Function Block Parameter List
Index Origin
Name
Store
Date Type
Default Value
0
STND DISCRETE_INPUT_BLOCK
SRW
Record
BLOCK
0
1
STND ST_REV
SR
Simple
UNSIGNED16
0
2
STND TAG_DESC
SRW
Simple
OCTET_STRING
“ “
3
STND STRATEGY
SRW
Simple
UNSIGNED16
0
4
STND ALERT_KEY
SRW
Simple
UNSIGNED8
0
5
STND MODE_BLK
SRW
Record
MODE
0x01;0x01;0x19;0x10
6
STND BLOCK_ERR
R
Simple
BIT_STRING
0
7
STND PV_D
R
Record
DISC_S
0;0
8
STND OUT_D
NRWO Record
DISC_S
0;0
9
STND SIMULATE_D
RW
Record
SIM_DISC
0;0;0;0;1
10 STND XD_STATE
SRW
Simple
UNSIGNED16
0
11 STND OUT_STATE
SRW
Simple
UNSIGNED16
0
12 STND GRANT_DENY
RW
Record
ACCESS_PERM
0;0
13 STND IO_OPTS|IO_OPTS_DI
SRW
Simple
BIT_STRING
0
14 STND STATUS_OPTS|STATUS_OPTS_DI
SRW
Simple
BIT_STRING
0
15 STND CHANNEL
SRW
Simple
UNSIGNED16
0
16 STND PV_FTIME
SRW
Simple
FLOATING_POINT
0
17 STND FIELD_VAL_D
R
Record
DISC_S
0;0
18 STND UPDATE_EVT
RW
Record
ALARM_EVENT
0;0;0,0;0;0;9;0
19 STND BLOCK_ALM
RW
Record
ALARM_DISC
0;0;0,0;0;0;0;8;0;0
20 STND ALARM_SUM|ALARM_SUM_DI
SRW
Record
ALARM_SUMMARY
0;0;0;0
21 STND ACK_OPTION|ACK_OPTION_DI
SRW
Simple
BIT_STRING
0
22 STND DISC_PRI
SRW
Simple
UNSIGNED8
0
23 STND DISC_LIM
SRW
Simple
UNSIGNED8
0
24 STND DISC_ALM
RW
Record
ALARM_DISC
0;0;0,0;0;0;0;7;0;0
Block
The functionality of these parameters follows the standard Fieldbus definitions as defined in the Foundation Fieldbus specifications.
8.11 Input Selector Function Block
IS Block Description
The signal selector block provides selection of up to four inputs and generates an output based on the configured action. This block normally
receives its inputs from AI blocks. The block performs maximum, minimum, middle, average and ‘first good’ signal selection. With a combi-
nation of parameter configuration options the block can function as a rotary position switch, or a validated priority selection based on the use
of the first good parameter and the disable_n parameter. As a switch the block can receive switching information from either the connected
inputs or from an operator input. The block also supports the concept of a middle selection. Although the normal configuration for this feature
would be with three signals the block should generate an average of the middle two if four signals are configured or the average of two if three
are configured and a bad status is passed to one of the inputs. Logic is provided for handling uncertain and bad signals in conjunction with
configured actions. The intended application of this block is to provide control signal selection in the forward path only, therefore, no back
calculation support is provided. SELECTED is a second output that indicates which input has been selected by the algorithm.
Logix 3400MD Digital Positioner LGENIM3405-02 11/13
48