6.8 Making Initial Checks
Identifying the Logix 3400 Digital Positioner
Before proceeding, verify the following to make sure that the user is communicating with the correct Logix 3400MD digital positioner:
•
Device type = 0 x 0203
•
Device ID = 464C530203-FLS-LX3400MD-00nnnnnnnn
•
Device tag, (tag description of the Logix 3400MD digital positioner)
•
Firmware revision level (revision level of the firmware elements)
Table 6.4 Logix 3400MD Digital Positioner Identification
Step
View Parameter
Verify
1
RS.DEV_TYPE
The value is = 0x0203
2
DEVICE_REVISION
DD_REVISION
The values are correct for the DD files provided.
3
Physical Device Tag
NOTE: The device tag name is not contained in a parameter. It can be set and
viewed using the field bus device configurator application.
The physical device tag is correct.
6.9 Configuration Tasks
Device Configuration Procedure Overview
A typical device configuration consists of the following tasks listed in Table 6.5 using the NI-FBUS Configurator application. Details on using
the configurator application are found in the NI-FBUS Configurator user manual supplied with the application software.
This procedure assumes that the hardware installation of the Logix 3400MD digital positioner is complete and the Logix 3400MD digital
positioner is powered up.
Table 6.5 Logix 3400MD Digital Positioner Configuration Task List
Task
Procedure
Result
1
2
Start the fieldbus process application
Start the fieldbus configurator application
Scans the fieldbus network and provides a listing of all active fieldbus devices on the network
or selected link.
Configurator windows are displayed on screen listing the active fieldbus devices.
3
Select a fieldbus device for configuration
4
5
Change the device and block tags, if desired.
Select/add/edit function blocks to create a function block
application process.
NOTE: Configure block objects in the following order:
1. Resource block
2. Transducer block
3. Analog Output block
4. PID block
Any unassigned tags are given a default tag name by the configurator.
Shows a representation of function blocks in the graphical interface window.
6
7
8
Connect (or wire) function blocks to define process loops.
Change block parameters, if necessary.
Configure trends and alarms
Linkages between function block inputs and outputs are created by using wiring tools. Pre-
configured templates can also be used.
Parameters changed for the process requirements.
Trending and alarms configured according to the process requirements.
9
Adjust the block execution schedule.
The function block execution schedule changed according to the process requirements.