Fail-safe handling, Ao block parameter list – Flowserve 400MD Logix User Manual
Page 45

The OUT parameter of the AO block is used to set the FINAL_POSITION_VALUE in the transducer block, as modified by the FINAL_VALUE_
RANGE.
READBACK_OUT tracks the valve position in percent.
Fail-safe Handling
The fail-safe parameters determine the response of an output block to the following conditions. FSTATE_TIME is the number of seconds
without communication or with Initiate Fail Safe at the CAS_IN status, required to put this block into the fail safe state. The FAULT_STATE
parameter of the resource block may also put this block into the fail safe state. The Failsafe Type I/O option determines whether the action is
simply to hold, or to move to FSTATE_VAL.
The Target to Manual if IFS I/O option may be used to latch the fail safe state when IFS appears in the CAS_IN status. This will cause a fail-safe
block alarm. After the cause of the IFS status is removed, the target mode may be returned manually to CAS mode when it is safe to do so
Section 10.17 described how to setup the fail-safe handling.
AO Block Parameter List
Table 8.8 lists the block parameters and default values for the AO function block.
Table 8.9 AO Function Block Parameter List
Index Origin
Name
Store
Date Type
Default Value
0
STND ANALOG_OUTPUT_BLOCK
SRW
Record
BLOCK
0
1
STND ST_REV
SR
Simple
UNSIGNED16
0
2
STND TAG_DESC
SRW
Simple
OCTET_STRING
“ “
3
STND STRATEGY
SRW
Simple
UNSIGNED16
0
4
STND ALERT_KEY
SRW
Simple
UNSIGNED8
0
5
STND MODE_BLK
SRW
Record
MODE
0x01;0x01;0x79;0x10
6
STND BLOCK_ERR
R
Simple
BIT_STRING
0
7
STND PV
R
Record
FLOAT_S
0;0.0
8
STND SP
NRW
Record
FLOAT_S
AO_VAL_SP_STATUS;AO_VAL_SP_VALUE
9
STND OUT
NRWO Record
FLOAT_S
0x80;0.0
10 STND SIMULATE
RW
Record
SIM_FLOAT
0;0.0;0;0.0;1
11 STND PV_SCALE
SRW
Record
SCALE
100.0;0.0;0;0
12 STND XD_SCALE
SRW
Record
SCALE
100.0;0.0;0;0
13 STND GRANT_DENY
RW
Record
ACCESS_PERM
0;0
14 STND IO_OPTS|IO_OPTS_AO
SRW
Simple
BIT_STRING
0
15 STND STATUS_OPTS|STATUS_OPTS_AO
SRW
Simple
BIT_STRING
0
16 STND READBACK
R
Record
FLOAT_S
0x80;0.0
17 STND CAS_IN
NRWI Record
FLOAT_S
0xC3;0.0
18 STND SP_RATE_DN
SRW
Simple
FLOATING_POINT
FLT_MAX
19 STND SP_RATE_UP
SRW
Simple
FLOATING_POINT
FLT_MAX
20 STND SP_HI_LIM
SRW
Simple
FLOATING_POINT
100
21 STND SP_LO_LIM
SRW
Simple
FLOATING_POINT
0
22 STND CHANNEL
SRW
Simple
UNSIGNED16
1
23 STND FSTATE_TIME
SRW
Simple
FLOATING_POINT
0
24 STND FSTATE_VAL
SRW
Simple
FLOATING_POINT
0
25 STND BKCAL_OUT
RO
Record
FLOAT_S
0xcc;0.0
26 STND RCAS_IN
NRW
Record
FLOAT_S
0x1C;0.0
27 STND SHED_OPT
SRW
Simple
UNSIGNED8
0
28 STND RCAS_OUT
R
Record
FLOAT_S
0xcc;0.0
29 STND UPDATE_EVT
RW
Record
ALARM_EVENT
0;0;0,0;0;0;9;0
30 STND BLOCK_ALM
RW
Record
ALARM_DISC
0;0;0,0;0;0;0;8;0;0
31 MFG
WSP
RW
Record
FLOAT_S
0,0.0
32 MFG
READBACK_OUT
RO
Record
FLOAT_S
0x80;0.0
33 MFG
AO_BLOCK_TEST
R
Array
UNSIGNED8
0,0,0,0,0,0,0,0
Logix 3400MD Digital Positioner LGENIM3405-02 11/13