Unit parameters – Flowserve 400MD Logix User Manual
Page 71

Parameter Name
Bit or Byte Values
Description
XD_FSTATE_OPT
No Bit 0x00
Bit 1 0x01
Bit 2 0x02
Fail to Last Known Set Point
Fail Valve Closed
Fail Valve Open
CONTROL_CONFIG
Bit 0 0X01
Bit 1 0x02
Bit 2 0x04
Bit 3 0x08
Bit 4 0x10
Bit 5 0x 20
Bit 6 0x40
Bit 7 0x80
Local Panel Disabled
Continuous Friction Mode Enabled
For Future Use
Pressure Control Enabled
Pressure Sensor Board Present
Single Action Enabled
For Future Use
For Future Use
MISC_CONFIG
Bit 0 0X01
Bit 1 0x02
Bit 2 0x04
Bit 3 0x08
Bit 4 0x10
Bit 5 0x 20
Bit 6 0x40
Bit 7 0x80
For Future Use
For Future Use
For Future Use
For Future Use
For Future Use
For Future Use
For Future Use
For Future Use
USER_INTERFACE_ACTIVE Bit 0 0X0001
Bit 1 0x0002
Bit 2 0x0004
Bit 3 0x0008
Bit 4 0x0010
Bit 5 0x 0020
Bit 6 0x0040
Bit 7 0x0080
Bit 8 0x0100
Bit 9 0x0200
Bit 10 0x0400
Bit 11 0x0800
Bit 12 0x1000
Bit 13 0x2000
Bit 14 0x 4000
Bit 15 0x8000
Air Action ATO Enabled
Characterization Linear
Auto Tune Enabled
Low Friction Mode
Calibration Auto
DIP SW 6 Spare
Up Button Not Pressed
Dn Button Not Pressed
Bit 1 of Gain Selector
Bit 2 of Gain Selector
Bit 3 of Gain Selector
For Future Use
Qucik Cal Button Not Pressed
For Future Use
For Future Use
For Future Use
LOAD_EE_DEFAULTS
0
1
2
Normal Operation
Reset Non-Volatile Variables
Reset Calibration Variables
CURVE_SELECT
0
1
2
Equal Percent
Quick Opening
Custom (CurveX,CurveY)
Unit Parameters
Table 8.27 Unit Parameters Table
Parameter Name
Bit or Byte Values
Description
TRAVEL_UNITS
57
Percent
PRESSURE_UNITS
6
7
10
12
PSI
BAR
Kg/cm
2
Kpa
INTERNAL_TMEP_UNITS
32
33
Deg C
Deg F
FRICTION_UNITS
0
Pounds
Logix 3400MD Digital Positioner LGENIM3405-02 11/13