5 block configuration errors, Configuration errors – Flowserve 400MD Logix User Manual
Page 84

9
NEEDS_MAINT_SOON
This indicates that the device needs maintenance soon. Diagnostics has indicated something is out of
tolerance or is going to fail, causing the positioner to possibly be operating with reduced functionality
(Transducer block only)
10
FAULT_STATE_SET
Indicates if the fault state has been set (Resource Block only)
11
LOCAL_OVERRIDE
Indicates if the block has gone into Local Override mode (LO)
12
SIMULATE_ACTIVE
The SIMULATE parameter is being used as the input to the AO block. This occurs if the simulate jumper is
set to Y on the electronics board and the ENABLE_DISABLE field of the SIMULATE parameter is set to 2
13
LINK_CONFIG_ERR
Set by the system. Indicates if all the links for the block configurations are available
14
BLOCK_CONFIG_ERR
Invalid parameter value in block. See Clearing Block configuration Errors
15
OTHER
* Depending on the fieldbus interface application, device operating status and parameter values may appear as text messages. The text in the table is typi-
cal of values or messages seen when using the NI-FBUS Configurator
Table 10.6: Transducer Block BLOCK_ERR diagnostics mapping
Diagnostic Flag
BLOCK_ERR Alarm Issued
POSITION_DEVIATION _ALARM
BLK_ERR_DEV_NEEDS_MAIN_NOW
FACTORY_RESET_STATE
BLK_ERR_DEV_NEEDS_MAIN_NOW
STROKE_CAL_REQUIRED
BLK_ERR_DEV_NEEDS_MAIN_NOW
SUPPLY_PRESS_LOW_ALARM
BLK_ERR_DEV_NEEDS_MAIN_NOW
LOSS_INTERBOARD_PCB
BLK_ERR_DEV_NEEDS_MAIN_NOW
MECHANICAL_STATUS not ZERO
BLK_ERR_DEV_NEED_MAINT_SOON
ELECTRONIC_STATUS not ZERO
BLK_ERR_DEV_NEED_MAINT_SOON
SUPPLY_PRESS_HIGH_WARNING
BLK_ERR_DEV_NEED_MAINT_SOON
SUPPLY_PRESS_LOW_WARNING
BLK_ERR_DEV_NEED_MAINT_SOON
PORT_A_VALUE_OUT_OF _RANGE
BLK_ERR_DEV_NEED_MAINT_SOON
PORT_B_VALUE_OUT_OF_RANGE
BLK_ERR_DEV_NEED_MAINT_SOON
PORT_A_RANGE_TOO_SMALL
BLK_ERR_DEV_NEED_MAINT_SOON
PORT _B_RANGE_TOO_SMALL
BLK_ERR_DEV_NEED_MAINT_SOON
PNUEMAITC_LEAK_WARN ING
BLK_ERR_DEV_NEED_MAINT_SOON
SPOOL_STICKING_WARNING
BLK_ERR_DEV_NEED_MAINT_SOON
SPOOL_STICKING_ALARM
BLK_ERR_DEV_NEED_MAINT_SOON
SPOOL_CYCLES_WARNING
BLK_ERR_DEV_NEED_MAINT_SOON
SPOOL_TRAVEL_WARNING
BLK_ERR_DEV_NEED_MAINT_SOON
HALL_SENSOR_UPPER_POSITION
BLK_ERR_DEV_NEED_MAINT_SOON
HALL_SENSOR_LOWER_POSITION
BLK_ERR_DEV_NEED_MAINT_SOON
FEEDBACK_RANGE_TOO_SMALL
BLK_ERR_DEV_NEED_MAINT_SOON
POSITION_OUT_OF_RANGE_LOW
BLK_ERR_DEV_NEED_MAINT_SOON
POSITION_OUT_OF_RANGE_HIGH
BLK_ERR_DEV_NEED_MAINT_SOON
NO_MOTION_TIME_OUT
BLK_ERR_DEV_NEED_MAINT_SOON
NON_SETTLE_TIME_OUT
BLK_ERR_DEV_NEED_MAINT_SOON
INNER_LOOP_OFFSET_TIME_OUT
BLK_ERR_DEV_NEED_MAINT_SOON
JOG_CALIBRATE_SET_100_POS
BLK_ERR_DEV_NEED_MAINT_SOON
10.5 Block Configuration Errors
Configuration Errors
Block configuration errors prevent a device block from leaving OOS mode. The BLOCK_ERR parameter (bit 1) shows whether a block configu-
ration error is present. Table 10.7 summarizes the conditions that may be the result of block configuration errors, which in turn cause a device
fault. Follow the recommended actions to correct these errors.
Logix 3400MD Digital Positioner LGENIM3405-02 11/13
84