5 temperature interconnection (rare use) – Daktronics GPR-12EV-RGB User Manual
Page 71

Temperature Sensor Mounting For 
GalaxyPro Revolution Displays 
page 3 of 4
5. Connect the cable coming from the
controller’s terminal block to the 
temperature sensor board in the 
temperature sensor housing. Refer to 
Figure 5 and the following table for 
wiring locations and connections at the 
sensor and to the controller. 
 
Figure 5: CAN Temperature Sensor Connection - 
M4 Controller 
6. Route cable around the sensor board as
shown in Drawing A-197884. 
 
7. Connect the cable and reassemble the
sensor.
 
Note: The cable length from the sensor to the 
last display should not exceed 500 feet. 
Primary – Controller 
Board (A31-TB1) 
Field 
Cabling 
CAN Temp 
Sensor (TB1) 
Pin 1 (+5V CAN)
Red
Pin 1
(+5V CAN)
Pin 2 (GND CAN)
Shield
Black
Pin 4
(GND CAN)
Pin 3 (CAN H)
Green
Pin 2 (CAN H)
Pin 4 (CAN L)
White
Pin 3 (CAN L)
1.5 Temperature Interconnection
(rare use)
In a primary to primary 
configuration, a 4-conductor 
shielded cable is needed to 
terminate the temperature sensor 
from one display to the other. 
 
One end terminates at the 4-position 
terminal block (TB1) on the primary 
display. The other end terminates at 
the 4-position terminal block (TB1) 
in the second display. Refer to 
Figure 6
and the following table for
correct interconnect locations. 
 
Note: Do not connect the wire to 
pin one on either display. 
In a primary to primary 
configuration, a 4-conductor 
shielded cable is needed to 
Figure 6: CAN Controller Interconnect – M4 Controller
DD1514799 Rev 0
29 January 2009
201 Daktronics Drive PO Box 5128, Brookings, SD 57006-5128
tel: 866-343-3122 fax: 605-697-4700
www.daktronics.com
