Important points about grounding – Daktronics GPR-12EV-RGB User Manual
Page 13
Power Installation
7
Installation with Ground and Neutral Conductors Provided
These displays are installed with ground and neutral conductors provided. The power cable
must contain an
isolated earth-
ground conductor.
Do not connect
neutral to ground at
the disconnect or at
the display. This will
violate electrical
codes and render the
warranty null and
void.
The display system
must be connected to
earth ground as
shown in Figure 7.
Proper grounding
protects the
equipment from
damaging electrical
disturbances and lightning. Daktronics requires a resistance to ground of 10 ohms or less.
The display must be properly grounded or the warranty will be null and void.
Important points about grounding:
•
Follow local and national codes: The material of an earth-ground electrode differs
from region to region and from conditions present at the site. Consult any electrical
codes that apply.
•
Support structure cannot be used as an earth-ground electrode: The support is
generally embedded in concrete, and if embedded in earth, the steel is either primed
or it corrodes, making it a poor ground.
•
One grounding electrode for each display face: Grounding is connected between
sections by bonding jumpers. Other grounding electrodes as described in national
and local electrical codes may be used.
•
Resistance to ground 10 ohms or less: This is required by Daktronics for proper
display performance. If the resistance to ground is higher than 10 ohms, it is
necessary to install additional grounding electrodes to reduce resistance. The
grounding electrode must be installed within 25 feet (7.6 m) of the display’s base and
must be connected to the ground lug on the back of the display, as shown in Figure
Figure 7: Correct Grounding