Power Installation

7

Installation with Ground and Neutral Conductors Provided

These displays are installed with ground and neutral conductors provided. The power cable

must contain an

isolated earth-

ground conductor.

Do not connect

neutral to ground at

the disconnect or at

the display. This will

violate electrical

codes and render the

warranty null and

void.

The display system

must be connected to

earth ground as

shown in Figure 7.

Proper grounding

protects the

equipment from

damaging electrical

disturbances and lightning. Daktronics requires a resistance to ground of 10 ohms or less.

The display must be properly grounded or the warranty will be null and void.

Important points about grounding:

Follow local and national codes: The material of an earth-ground electrode differs

from region to region and from conditions present at the site. Consult any electrical

codes that apply.

Support structure cannot be used as an earth-ground electrode: The support is

generally embedded in concrete, and if embedded in earth, the steel is either primed

or it corrodes, making it a poor ground.

One grounding electrode for each display face: Grounding is connected between

sections by bonding jumpers. Other grounding electrodes as described in national

and local electrical codes may be used.

Resistance to ground 10 ohms or less: This is required by Daktronics for proper

display performance. If the resistance to ground is higher than 10 ohms, it is

necessary to install additional grounding electrodes to reduce resistance. The

grounding electrode must be installed within 25 feet (7.6 m) of the display’s base and

must be connected to the ground lug on the back of the display, as shown in Figure

7.

Figure 7: Correct Grounding